7
Technical data
MOVITRAC® B technical data
Operating Instructions Basic Unit – MOVITRAC
®
B
37
7.4.6
AC 400 / 500 V / 3-phase / size 0S / 0.55 ... 1.5 kW / 0.75... 2.0 HP
MOVITRAC
®
MC07B (3-phase supply system)
0005-5A3-
4-00
0008-5A3-
4-00
0011-5A3-
4-00
0015-5A3-
4-00
Part number
828 517 9
828 518 7
828 519 5
828 520 9
INPUT
Permitted rated supply voltage
V
N
3 × AC 400 V
V
Mains
= AC 380 V – 10 % ... AC 500 V + 10 %
Rated supply frequency
f
N
50 / 60 Hz ± 5 %
Rated mains current 3-phase with
V
Mains
= AC 400 V
AC 1.8 A
AC 2.2 A
AC 2.8 A
AC 3.6 A
OUTPUT
Output voltage
V
A
3 × 0 ... V
Mains
Recommended motor power under constant
load (with V
Mains
= AC 400 V)
P
Mot
0.55 kW
0.75 HP
0.75 kW
1.0 HP
1.1 kW
1.5 HP
1.5 kW
2.0 HP
Rated output current
with V
Mains
= AC 400 V
I
N
AC 2.0 A
AC 2.4 A
AC 3.1 A
AC 4.0 A
Minimum permitted braking resistor value
(4-Q operation)
R
BW_min
68
Ê
GENERAL INFORMATION
Power loss at I
N
P
V
42 W
48 W
58 W
74 W
Current limitation
150 % I
N
for maximum 60 seconds
Connections
Terminals
4 mm
2
/ AWG12
Dimensions
W × H × D
80 × 185 × 163 mm / 3.1 × 7.3 × 6.4 in
Weight
m
1.5 kg / 3.3 lbs.
80
163.5
185
196
236
220
70
159.5
149
6
P
i
f
kVA
Hz
n