![SEW-Eurodrive MOVIPRO SDC Manual Download Page 17](http://html.mh-extra.com/html/sew-eurodrive/movipro-sdc/movipro-sdc_manual_1250182017.webp)
Manual – MOVIPRO® SDC with DeviceNet Interface
17
4
Fieldbus connection
Installation Notes
4.1.2
X4242: DeviceNet output
The following table provides information about this connection:
Bus termination
Connection com-
ponent
The following table shows the available component for this connection:
4.1.3
MOVIPRO
®
– DeviceNet connection
The DeviceNet specification stipulates a line structure for the bus. The maximum per-
mitted cable length depends on the baud rate setting:
Function
DeviceNet output
Connection type
M12, 5-pole, female, A-coded
Wiring diagram
2264816267
Assignment
No.
Name
Function
1
Drain
Shield/equipotential bonding
2
V+
DC 24 V output
3
V-
Reference potential
4
CAN_H
CAN data line (high)
5
CAN_L
CAN data line (low)
1
4
3
2
5
INFORMATION
If the unit is the last station in the bus, you must provide for a bus termination by con-
necting an according resistor to plug connector X4242.
Connection component
Resistor network
Part number 1 328 703 6
Connection: M12
Baud rate
Maximum cable length
125 kBaud
500 m
250 kBaud
250 m
500 kBaud
100 m