Electrical installation
Electrical connections
Operating Instructions – MOVIPRO
®
PHE..B-A15-.1X0..B-00
46
6.10.4
X1261: AC 400 V contact conductor connection
WARNING
Electric shock from blank live connections.
Severe or fatal injuries.
•
Use safe, insulated female push-on connectors for installation.
•
To avoid coming into contact with unused male push-on connectors, you have to
install the touch guard on unused male push-on connectors.
WARNING
Electric shock from live connections.
Severe or fatal injuries.
•
Note the following points for selecting suitable female push-on connectors:
•
Use safe, insulated female push-on connectors for installation.
•
The installed female push-on connectors must comply with the standard
DIN 46 245 part 3, DIN 46 247 part 3 or DIN 46 346 part 3.
•
Use the female push-on connector only with the insulating housing specified by
the manufacturer.
•
Make sure that each female push-on connector is plugged in correctly and
latched.
•
The latching function of the female push-on connector cannot be guaranteed for
multiple use. Therefore, use a new female push-on connector after single use.
NOTICE
Damage caused by corrosion.
Damage of connection X1261.
•
The push-on contacts of connection X1261 are accessible from the outside. En-
sure that the push-on contacts do not come into contact with water or other cor-
rosive substances.
Function
AC 400 V connection for units with half-wave control supplied by the conductor rail
Connection type
Male push-on connectors 6.3
Connection image
1
2
3
4
9
8
5
6
7