6
Electrical installation
Electromagnetic compatibility (EMC)
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
59
6.5
Electromagnetic compatibility (EMC)
For further information on EMC compliant installation, refer to the following documen-
tation: "Drive Engineering – Practical Implementation, Electromagnetic Compatibility
(EMC) in Drive Engineering".
6.5.1
EMC category
INFORMATION
The product can cause EMC interference within the permitted limit range according to
EN 61800‑3.
The product is a drive system of category C3 (see EN 61800‑3).
6.5.2
EMC-compliant installation
Ensure that there is a HF-capable equipotential bonding for all drive components. Use
low-impedance, HF-capable connectors such as HF litz wire or ground straps. Stan-
dard PE does not achieve sufficient equipotential bonding regarding HF and EMC. For
more information, refer to chapter "Installing ground connection or equipotential bond-
ing" (→
[1]
[4]
[3]
[3]
[3]
[3]
[3]
[3]
[3]
[2]
[3]
[3]
[3]
[3]
[1]
[5]
9007232480091915
[1]
HF litz wire, ground strap
[4]
Machine base
[2]
Product
[5]
Cable duct
[3]
PE conductor
26596598/EN – 10/2020