5
Electrical installation
Installation instructions
Operating Instructions – MOVIMOT
®
flexible
52
5.3.6
Activating terminals X3 for the braking resistor
Adhere to the following sequence when you activate the terminals X3 for the braking
resistor:
Terminals X3 for the braking resistor (the following figure shows a schematic
illustration)
1.
2.
25650172171
5.3.7
Activating control terminals X9
Adhere to the following sequence when you activate the X9 control terminals:
X9 control terminals (the following figure shows a schematic illustration)
2.
1.
3.
25657187979
5.3.8
Residual current device
WARNING
No protection against electric shock if an incorrect type of residual current device is
used.
Severe or fatal injuries.
•
The product can cause direct current in the PE conductor. If a residual current
device (RCD) or a residual current monitoring device (RCM) is used for protec-
tion in the event of a direct or indirect contact, only a type B RCD or RCM is per-
mitted on the supply end of the product.
•
If the use of a residual current device is not mandatory according to the standards,
SEW‑EURODRIVE recommends not to use a residual current device.
29128668/EN – 12/2019