5
Electrical installation
Installation instructions
Operating Instructions – MOVIGEAR
®
performance
71
5.3.9
Notes on PE connection
WARNING
Electric shock due to incorrect connection of PE.
Severe or fatal injuries.
•
The permitted tightening torque for the screw is 2.0 to 2.4 Nm.
•
Observe the following notes regarding PE connection.
Make sure the lifting eye has been removed before you connect the PE cable.
Store the lifting eyes for future service work.
5 m
in
X5
13
3_1 X
51
33
_2
2.0 – 2.4 Nm
9007225026665867
Impermissible assembly
Recommendation:
Assembly with cable lug
1)
Permitted for all cross sections
Assembly with solid connecting
wire
1)
Permitted for cross sections up
to
max. 2.5 mm
2
[1]
M5
9007201632429067
2.5 mm²
M5
9007201632413579
1) Use the specified material for the assembly that is included in the accessory bag.