Fault table standard
Operating Instructions – MOVIGEAR
®
performance
212
Subfault: 35.2
Description: Application level too low
Response: Emergency stop + output stage inhibit
Cause
Measure
The activated software module requires a higher
application level.
Enter an activation key for the required applica-
tion level. You can find the required level in the
parameter 8438.3 "Application level – Required
level".
Subfault: 35.3
Description: Technology level too low
Response: Emergency stop + output stage inhibit
Cause
Measure
An activated technology function requires a
higher technology level.
Enter an activation key for the required techno-
logy level. You can find the required level in the
parameter 8438.13 "Technology level – Required
level".
Subfault: 35.4
Description: Activation key – technology level invalid
Response: Emergency stop + output stage inhibit
Cause
Measure
The activation key was entered incorrectly.
Enter the activation key again.
The activation key was not created for this
device.
Check the activation key.
When using a double axis, the activation key for
the wrong instance was entered in the device.
Enter the activation key for the allocated instance.
An activation key for an application level was
entered in the parameter "Technology level – Ac-
tivation key".
Enter the activation key in the correct parameter.