8
Service
Fault table standard
Operating Instructions – MOVIGEAR
®
performance
188
Subfault: 19.2
Description: Position setpoint violation
Response: Application stop + output stage inhibit
Cause
Measure
Position setpoint outside software limit switches.
Check the position setpoint.
Position setpoint outside modulo range.
Check the position setpoint.
Position in user unit generates number overflow
in system unit.
Check position in user unit.
Subfault: 19.3
Description: Speed setpoint violation
Response: Application stop + output stage inhibit
Cause
Measure
Specified rotational speed setpoints not plausible. Adjust rotational speed setpoints.
Subfault: 19.4
Description: Acceleration setpoint violation
Response: Emergency stop + output stage inhibit
Cause
Measure
The specified acceleration setpoints are not
plausible. Only a value range of >= 0 is permitted.
Adjust acceleration setpoints.
Subfault: 19.5
Description: Drive function does not exist
Response: Application stop + output stage inhibit
Cause
Measure
Non-existing drive function (FCB) selected via
process data.
Specify an existing FCB number for FCB activa-
tion via process data.
Subfault: 19.6
Description: Mass moment of inertia setpoint violation
Response: Emergency stop + output stage inhibit
Cause
Measure
Implausible values specified as mass moment of
inertia setpoints. Only a value range of >= 0 is
permitted.
Adjust the setpoints for the mass moment of iner-
tia.
Subfault: 19.7
Description: Referencing missing
Response: Application stop + output stage inhibit
Cause
Measure
Activated function only permitted with referenced
encoder.
Reference the encoder first, then activate the
function.