Operating Instructions – MOVIGEAR® DAC-B
167
9
Transmitting individual parameters via AS-Interface
Communication with AS-Interface Double Slave GLK31A
Deactivating the
mechanical control
elements
You have to deactivate the mechanical control elements because parameterization of
the MOVIMOT
®
is to be carried out via AS-Interface. To do so, write the value 65535
dec
= 0xFFFF to parameter
10096.0
.
"Write request" service:
The slave replies after the system-related telegram runtime.
"Write response OK" response telegram:
Once the GLK31A double slave has correctly received the data, it immediately sends
the response 0x51 "Write response OK" to the master. Simultaneously, the MOVILINK
®
protocol is sent to the MOVIGEAR
®
inverter.
CTT2 service
MOVILINK
®
protocol
Code
Index Length Addres
sing
Man-
age-
ment
Sub-
index
Index
high
Index
low
MSB
data
Data
Data
LSB
data
0x11
0x02
0x09
0x00
0x32
0x1E
0x27
0x70
0x00
0x00
0xFF
0xFF
Code 0x11 =
Write request
Index 0x02 =
MOVILINK
®
parameter service
Length 0x09 =
Length of the MOVILINK
®
protocol
Addressing 0x00 =
Addressing the command pcb because this is where the parameter is stored.
Management 0x32 =
Write parameter
Subindex 0x1E =
Subindex of the parameter
Index High 0x27 =
High value of the index
Index Low 0x70 =
Low value of the index
=> Index of the parameter = 10096
dec
= 0x2770
hex
The value 0x2770
hex
is written on the index high and index low bytes.
Data MSB 0x00
The parameter must be set to 65535
dec
= 0xFFFF to deactivate the mechanical
control elements.
This value is written to the 4 data bytes.
Data 0x00
Data 0xFF
Data LSB 0xFF
CTT2 service
Code
0x51
Code 0x51 =
Write response OK