Manual – MOVIDRIVE® MDX61B MOVI-PLC® DHP11B Control Card
61
6
Project planning for a C1 master
DP-V1 Functions
6.4
Project planning for a C1 master
The GSD file
SEW-6007.GSD
is required for the project planning of a DP-V1 C1 master.
This file activates the DP-V1 functions of the DHP11B control card.
Operating mode
(DP-V1 mode)
The DP-V1 operating mode is usually activated during project planning for a C1 master.
All DP slaves, which have the DP-V1 functions enabled in their GSD file and which sup-
port DP-V1, will be operated in the DP-V1 mode. Standard DP slaves will still be run via
PROFIBUS-DP. This ensures mixed mode is run for DP-V1 and DP-capable modules.
Depending on the specification of the master functionality, a DPV1-capable station that
was configured using the DPV1 GSD file can run in the DP operating mode.
6.5
Appendix
Program exam-
ple for SIMATIC
S7
The STEP7 code stored in the GSD file shows how parameters are accessed via the
STEP7 system function blocks SFB 52/53. You can copy the STEP7 code and
import/compile it as STEP7 source.
Technical data
DP-V1 for the
DHP11B control
card
0x18
Number of values is not
consistent
Write request: Number of parameter data
values that do not match the number of
elements in the parameter address
0
0x19
axis nonexistent
Access to an axis which does not exist
-
up to 0x64
Reserved
-
-
0x65..0xFF
Manufacturer-specific
-
-
Error no.
Meaning
Used at
Supplem. Infor-
mation
GSD file for DP-V1:
SEW-6007.GSD
Module name for project planning:
MOVI-PLC
Number of parallel C2 connections:
2
Supported data set:
Index 47
Supported slot number:
Recommendation: 0
Manufacturer code:
10A hex (SEW-EURODRIVE)
Profile ID:
0
C2 response timeout
1s
Max. length C1 channel:
240 byte
Max. length C2 channel:
240 byte