5
Process data exchange with the DHP11B control card
PROFIBUS-DP Operating Characteristics
5
PROFIBUS-DP Operating Characteristics
This section describes the basic characteristics of the DHP11B control card connected
to the PROFIBUS-DP system.
5.1
Process data exchange with the DHP11B control card
The DHP11B control card is controlled via the process data channel which is up to 32
I/O words in length. These process data words are mapped in the I/O or peripheral area
of the DHP11B control card, for example when a master PLC is used as the DP master.
As a result, the process data words can be addressed in the usual manner.
Control example
for Simatic S7
The exchange of process data with the DHP11B control card is controlled using Simatic
S7 in accordance with the selected process data configuration either directly using load
and transfer commands or by means of special system functions,
SFC 14 DPRD_DAT
and
SFC15 DPWR_DAT
.
20065AXX
Figure 15: Mapping PROFIBUS data in the PLC address range
PW160
PW160
PA 3
PE 3
PA 2
PE 2
PA 1
PE 1
PW158
PW158
PW156
PW156
PW154
PW154
PW152
PW152
PW150
PW150
PW148
PW148
X31
X32
X33
X30
X34
20
21
22
23
24
25
26
DHP11B
1
2
3
1
2
3
1
2
3
2
3
1
PA 1
PE 1
PE 2
PA 2
PE 3
PA 3
PE 32
PA 32
[2]
[1]
[1]
[1]
8 byte MOVILINK
®
parameter channel
[2]
Address range of the master PLC
PE1 ... PE32
Process input data
PA1 ... PA32
Process output data
For additional information on programming and project planning, refer to the
README_GSD6007.PDF file included in the GSD file.