![SEW-Eurodrive MOVIDRIVE MOVI-PLC DHP11B Manual Download Page 12](http://html.mh-extra.com/html/sew-eurodrive/movidrive-movi-plc-dhp11b/movidrive-movi-plc-dhp11b_manual_1250110012.webp)
12
Manual – MOVIDRIVE® MDX61B MOVI-PLC® DHP11B Control Card
3
Connection and terminal description of the DHP11B control card
Assembly / Installation Instructions
3.2
Connection and terminal description of the DHP11B control card
Part number
Optional control card DHP11B: 1 820 472 4
You can plug the DHP11B control card into the MOVIDRIVE
®
MDX61B drive inverter
but not into the MOVIDRIVE
®
MDX60B drive inverter.
Only plug the DHP11B control card into the fieldbus slot or expansion slot of the
MOVIDRIVE
®
MDX61B drive inverter.
Front view
DHP11B control card
Designation
LED
DIP switch
Terminal
Function
20052AXX
LEDs
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
24V / I/O OK
PLC status
IEC progr. status
Run Profibus
Fault Profibus
CAN 2 status
CAN 1 status
Status of voltage supply I/O
Status of control firmware
Status of control program
Status of PROFIBUS bus electronics
Status of PROFIBUS communication
Status of CAN 2 system bus
Status of CAN 1 system bus
Terminal X31:
Binary inputs and outputs
X31:1
X31:2
X31:3
X31:4
X31:5
X31:6
X31:7
X31:8
X31:9
X31:10
X31:11
X31:12
+ 24 V input
REF24V
DIO 0
DIO 1
DIO 2
DIO 3
DIO 4
DIO 5
DIO 6
DIO 7
VO24
REF24V
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Voltage output DC+24V
Reference potential for binary signals
Terminal X32:
CAN 2 system bus
connection
(electrically isolated)
X32:1
X32:2
X32:3
REF_CAN 2
CAN 2H
CAN 2L
Reference potential for system bus CAN
2
System bus CAN 2 high
System bus CAN 2 low
Terminal X33:
CAN 1 system bus
connection
X33:1
X33:2
X33:3
DGND
CAN 1H
CAN 1L
Reference potential for system bus CAN
1
System bus 1 high
System bus 1 low
Terminal X30:
PROFIBUS connection
X30:9
X30:8
X30:7
X30:6
X30:5
X30:4
X30:3
X30:2
X30:1
GND (M5V)
RxD/TxD-N
N.C.
VP (P5V/100 mA)
GND (M5V)
CNTR-P
RxD/TxD-P
N.C.
N.C.
Reference potential for PROFIBUS
Signal receive transmit negative
Terminal unassigned
DC+5 V potential for bus terminator
Reference potential for PROFIBUS
PROFIBUS control signal for repeater
Signal receive transmit positive
Terminal unassigned
Terminal unassigned
Terminal X34:
RS485 interface
X34:4
X34:3
X34:2
X34:1
DGND
RS-
RS+
5V
Reference potential
RS485 - signal
RS485 + signal
Voltage output DC+5 V
DIP switches
for setting
the PROFIBUS
Station address
2
0
2
1
2
2
2
3
2
4
2
5
2
6
Significance: 1
Significance: 2
Significance: 4
Significance: 8
Significance: 16
Significance: 32
Significance: 64
DHP11B
X31
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
X32
X33
X30
X34
2
0
2
1
2
2
2
3
2
4
2
5
2
6
1
3
1
2
3
1
2
3
1
1
2
1
2
3
1
2
3