14
MOVIDRIVE
®
PROFIBUS DFP11A
2
Assembly / Installation
Instructions
2.
Switch on 24 V supply
Switch on the external 24 V supply only (not the mains supply!) to program the drive inverter.
3.
Setpoint source = FIELDBUS / control source = FIELDBUS
Set the setpoint source and the control source to FIELDBUS to control the drive inverter via
fieldbus.
4.
Input terminals DIØ1 ... DIØ3 = NO FUNCTION
Program the input terminals to NO FUNCTION.
For more information on commissioning and controlling the MOVIDRIVE
®
drive inverter please
refer to the Fieldbus Unit Profile Manual.
P100 Setpoint source = FIELDBUS
P101 Control source = FIELDBUS
P600 Programming terminal DIØ1 = NO FUNCTION
P601 Programming terminal DIØ2 = NO FUNCTION
P602 Programming terminal DIØ3 = NO FUNCTION