12
MOVIDRIVE
®
PROFIBUS DFP11A
2
Assembly / Installation
Instructions
Table 1: Meaning of the visual signals of the RUN and BUS FAULT LEDs
The option pcb has two LEDs for status and fault indication of the option pcb and the connected
bus system (Fig. 2). Table 1 shows the meaning of the visual signals of these LEDs. While the
green LED “RUN” indicates the operational status of the option pcb, the red LED “BUS FAULT”
indicates the status of the PROFIBUS connection.
2.9
GSD File
All slave-specific features are stored in a device database file (GSD file). EN 50170 V2 / DIN E
19245 Part 3 describes the format of a GSD file. It can be used by the DP master for easy configu-
ration of the DP slave. However, as some DP masters do not support this file format, additional
type files are required. These files are enclosed to the fieldbus documentation package on a
diskette. In addition, these files can be downloaded via modem or the Internet at the addresses
below:
Internet:
http://www.SEW-EURODRIVE.com (all files)
http://www.PROFIUS.com (GSD files only)
Modem:
Siemens Schnittstellencenter Fürth
Tel.: +49 (911) 737972 (GSD and Siemens type files)
On
Off
DP mode: The drive inverter is in data exchange mode.
FMS mode: There is an active FMS link between the FMS master and the drive inverter.
Mixed mode FMS/DP: Combination of the above
On + flickering
Off
The drive inverter is being parameterized via PROFIBUS-DP or -FMS (Read/Write
access operations)
Off
On
Hardware fault on the DFP11 option pcb
Flashing at approx.
1 Hz
Flashing at approx. 1 Hz
Hardware fault on the DFP11 option pcb
Flashing at approx.
1 Hz
On
Check the firmware version of the control pcb (basic unit).
LED Green RUN LED Red BUS FAULT
Meaning