Installation instructions for the basic unit
Installation
Cross sections
•
Supply system lead: Cross section according to rated input current I
mains
at rated
load.
•
Motor lead: Cross section according to rated output current I
rated
.
•
Electronics cables:
MCF/MCV/MCS:
For single cores 0.20...2.5 mm
2
(AWG 24...12)
For double cores 0.20...1 mm
2
(AWG 24...17)
MCH:
Only single cores 0.20...1.5 mm
2
(AWG 24...12)
Use right-angled crimping pliers with 1.5 mm
2
(AWG 16)
Unit output
Connecting
braking resistors
•
Use two tightly twisted leads or a 2-core shielded power cable. Cross section ac-
cording to the rated output current of the inverter.
•
Protect the braking resistor with a bimetallic relay / thermal overload relay (
→
Wir-
ing diagram for basic unit, power section and brake). Set the trip current according
to the technical data of the braking resistor. SEW-EURODRIVE recommends us-
ing an overcurrent relay of trip class 10 or 10A in accordance with EN 60947-4-1.
•
For braking resistors of the BW...-T / BW...-P series, the integrated temperature
switch/overcurrent relay can be connected using a 2-core shielded cable as an
alternative to a bimetallic relay.
•
Install the flat-type braking resistors together with the appropriate touch guard.
Installing braking
resistors BW... /
BW..-T / BW...-P
•
Permitted mounting options:
– on horizontal surfaces
– on vertical surfaces with brackets at the bottom and perforated sheets at top and
bottom
•
Mounting not permitted:
– on vertical surfaces with brackets at the top, right or left
STOP!
MOVIDRIVE
®
can suffer irreparable damage if you connect capacitive loads.
•
Only connect ohmic/inductive loads (motors).
•
Never connect capacitive loads.
60135AXX
Figure 97: Only connect ohmic/inductive loads; do not connect capacitive loads