5
Electrical installation
Installation instructions
Operating Instructions – MOVI-C
®
FIELD CONTROLLER standard/advanced
40
5.3.4
Actuating the line terminals X1_a, X1_b
Adhere to the following sequence when actuating the line terminals X1_a and X1_b:
Line terminals X1_a and X1_b
(the following figure shows a schematic illustration)
2.
1.
25649924107
5.3.5
Actuating control terminals X9
Adhere to the following sequence when actuating the X9 control terminals:
X9 control terminals (the following figure shows a schematic illustration)
2.
1.
3.
28713963147
5.3.6
Residual current device
WARNING
No protection against electric shock if an incorrect type of residual current device is
used.
Severe or fatal injuries.
• The product can cause direct current in the PE conductor. If a residual current
device (RCD) or a residual current monitoring device (RCM) is used for protec-
tion in the event of a direct or indirect contact, only a type B RCD or RCM is per-
mitted on the supply end of the product.
• If the use of a residual current device is not mandatory according to the standards,
SEW‑EURODRIVE recommends not to use a residual current device.
26872137/EN – 12/2021