5
Startup
Startup of "standard configuration"
Manual – ECDriveS
®
21
5.1.4
Assigning the PROFINET device name
In the TIA Portal, the PROFINET device name, the IP address, and the subnet mask
are modified according to the specifications.
[2]
[1]
25138728203
[1]
Fieldbus controller
[2]
Menu command [Assign device name]
1. Right-click on the relevant fieldbus controller [1] in the TIA Portal.
2. Select the [Assign device name] [2] menu command from the context menu.
ð
The PROFINET device name, the IP address, and the subnet mask are as-
signed to the fieldbus controller.
5.1.5
Assigning the "Update time" and "Watchdog time"
In "ZPA mode", the ECC-DFC fieldbus controllers communicate with each other. In
connection with short update times, this can cause network problems. Therefore se-
lect an "Update time" ≥32 ms.
The length of the "Watchdog time" is a multiple of the update time. The default value
(3) is suitable for all operating modes.
25137311371
25938274/EN – 01/2019