14
Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
4
Setting the DIP switches
Assembly and Installation Notes for Ethernet
4.5
Setting the DIP switches
2
0
(Def IP)
if the switch "2
0
" is set to "1" (= right = ON), the following default IP address parameters
are set when the DC 24 V backup voltage is switched on.
• IP address: 192.168.10.4
• Subnet mask: 255.255.255.0
• Default gateway: 192.168.10.4
• P785 DHCP / Startup configuration: Saved IP parameters (DHCP is deactivated)
2
1
(protocol)
DIP switch "2
1
" is used to set the protocol that is used for communication.
• 2
1
= "1" (= right = ON): The EtherNet/IP and Modbus TCP/IP fieldbus protocol is
active.
• 2
1
= "0" (= left = OFF): The PROFINET fieldbus protocol is active.
TIP
Before each change to the DIP switches, disconnect the MOVI-PLC
®
advanced
DHR41B control card from the voltage supply. The DIP switch settings are adopted
during initialization only.
64248AXX
DHR41B
2
2
0
1
ON