10
Technical data and dimension drawings
Port overview
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
80
Stand-alone device
Electrical supply
•
X26: V = DC 24 V (–15% / +20%), DGND must be grounded (PELV)
•
Power consumption P
max
= 8.5 W, I
max
= 600 mA
•
X31: Supply the digital inputs and outputs separately with DC 24 V.
INFORMATION
•
The CAN 1 system bus is connected in parallel to X33 and X26.
•
The RS485 interface COM 1 is connected in parallel to X34 and X24.
•
For further technical data, refer to chapter
"
Technical data of the DH.21B/41B
76).
10.6
Port overview
10.6.1
PROFINET
Port
TCP/
UDP
Function
Authorization
Ethertype 8892hex
Process data exchange
Controlling connection
Dynamic
port defini-
tion via End
Point Map-
per
UDP
PROFINET DCE/RPC
Reading and writing on all indexed parameters
23
TCP
Telnet
Reading OEM diagnostic data
80
TCP
http
The Java application uses SMLP via Port 300,
reading and writing IP parameters,
reading and writing indexed parameters
161
UDP
SNMP
Reading on MIBs
300
TCP
SMLP (MOVILINK
®
on Ethernet)
Reading and writing of all parameters
300
UDP
Address Editor
Reading and writing the IP parameters
10.6.2
EtherNet/IP™, Modbus/TCP
Port
TCP/
UDP
Function
Authorization
Ethertype 80E1hex ODVA ring redundancy protocol DLR
Reading and writing the ring redundancy para-
meter
23
TCP
Telnet
Reading OEM diagnostic data
80
TCP
http
The Java application uses SMLP via Port 300,
reading and writing IP parameters,
reading and writing indexed parameters
300
TCP
SMLP (MOVILINK
®
on Ethernet)
Reading and writing of all parameters
300
UDP
Address Editor
Reading and writing the IP parameters
22900055/EN – 08/2016