Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
32
Assignment
No.
Name
Function
Color cod-
ing
X30D
1
V–
0V24
BK
2
CAN_L
CAN_L
BU
3
SHIELD
SHIELD
blank
4
CAN_H
CAN_H
WH
5
V+
+24 V
RD
Setting the station address
To set the DeviceNet
TM
station address, use DIP switches 2
0
– 2
5
on the DHF21B/41B
option card. The DHF21B/41B option card supports address range 0 – 63.
INFORMATION
Always de-energize the DHF21B/41B option card before changing the DIP switch
setting. The DIP switch settings are only adopted during initialization.
DHF41B
2
2
2
2
0
1
2
3
2
2
2
4
5
6
27
ON
2103383051
2
0
– 2
5
= MAC ID setting
2
6
– 2
7
= baud rate setting
Setting the MAC ID
The MAC ID (
M
edia
A
ccess
C
ontrol
Id
entifier) is set on the DHF21B/41B option card
using DIP switches 2
0
– 2
5
in a binary coded manner. The MAC ID represents the
node address of the DHF21B/41B option card. The DHF21B/41B option card supports
address range 0 – 63.
Setting the baud rate
The baud rate is set using DIP switches 2
6
and 2
7
.
DIP switch
Baud rate
2
6
2
7
0
0
125 kBd
1
0
250 kBd
0
1
500 kBd
1
1
Invalid
A maximum of 64 DeviceNet
TM
data words can be exchanged between the
DeviceNet
TM
module and the UFF41B option. The number is set using the DeviceNet
TM
scanner.
22900055/EN – 08/2016