Operating Instructions – Explosion-Proof CMP Synchronous Servomotors
5
Wiring information
Electrical Installation
The right-angle connectors can be rotated to achieve the required position.
Different positions of the adjustable connectors
5.8
Wiring information
5.8.1
Protecting the brake control system against interference
To protect the brake control system against interference, do not route unshielded brake
cables together with switched-mode power cables.
Switched-mode power cables include in particular:
• Output cables from inverters, converters, soft start units and brake units
• Supply cables to braking resistors and similar.
5.8.2
Thermal motor protection
5.8.3
Special aspects for operation with a servo inverter
When servomotors are powered from inverters, the wiring instructions issued by the in-
verter manufacturer must be followed. Observe section "Operation" on page 37 And the
operating instructions for the inverter.
NOTE
The connector should only be rotated to install and connect the servomotor. Do
not
expose
the connector to permanent motion once it has been installed.
63406AXX
STOP!
Install the connecting lead of the KTY separately from other power cables, maintaining
a distance of at least 200 mm. The cables can only be routed together if either the KTY
cable or the power cable is shielded.