8
Fig. 3-4 Removing bezel from the base
Plumbing and Wiring to the Electrical Box (Rough in)
Flush mounting:
Use a 3 gang electrical box RACO 697 or equivalent or mount directly into the wall. If mounting directly
into the wall create an opening approximately 2.8” (71 mm) by 5.4” (134 mm). If using the 3 gang box
use #6 machine screws to mount the ears of the SRIM rear housing to the electrical box. If mounting
directly into the wall without an electrical box, use drywall screws to mount the 4 ears of the SRIMV
box to the wall.
Fig. 3-5 Rough Plumbing and Wiring to Rough-in box, Flush Mount Unit