background image

Installation Guide

“Multi-Sense” Model 260 Series

Multi-Range Differential Pressure Transducer

GENERAL INFORMATION

Every Model 260 has been calibrated and tested before shipment to guarantee
performance for all pressure ranges.

The Model 260 is available in four versions, which have field selectable range
capability via a slide switch.  See four versions below:

MULTI-SENSE RANGE SPECIFICATIONS

The Model 260 is available in four field selectable output configurations.  See four
versions below:

SIMPLE 5-STEP SETUP INSTRUCTIONS - STEPS 2 - 5

Power On - LCD Display

Display momentarily toggles thru all existing setup parameters on initial power
up. Pressure is normally indicated on display.  Units are either in inches of water
column (WC) MS1 & MS2, or Pascal (Pa) MS3 & MS4.

Multi-Sense Voltage

3-Wire, 1-5, 0-5, 0-10 VDC Configuration

Model 260

Multi-Sense Current

2-Wire, 4-20 mA Configuration

 

  

+

RANGE:

1   0.5   0.25   0.1

UNI/BI

 ZERO

mA/1-5V/5V /10V

 

+

-

2601MS1

S/N:

 EXC COM OUT

Date Code

*STEP 2:

 

Select Pressure Range

: Set

appropriate full scale range using
the 

Slide Switch Multiplier.

LCD will momentarily indicate
selected range.

STEP 5:

 

Push Button

Zero

 - While at

zero pressure
Press and hold
the 

Zero Push

Button

 for 1

second to
automatically
reset output to
zero.

STEP 3:

 

Select Unidirectional

or Bi-directional mode.

STEP 4: Select Current (mA)

or Voltage 1-5, 0-5, or
0-10 VDC output range.

STEP 1:

 

Wire and Power Up Unit 

- Follow diagrams

below for 2-wire and 3-wire configurations.
After completing wiring requirements - Apply
power to the Model 260.

SIMPLE 5-STEP SETUP INSTRUCTIONS -
STEP 1
ELECTRICAL CONNECTIONS

-

 EXC

COM

OUT

Power

Supply

13 - 30V

-

24V AC/DC

Nominal

Excitation

-

Model C260

 +

-

 EXC

COM

OUT

 +

-

24V (DC Only)

Nominal

Excitation

 +

-

X

Typical 250 Ohm

Sense Resistor
for 1-5V Output

Measurement

Voltage
Monitor

Power

Supply

13 - 30V

Current
Monitor

Removable Terminal Block for Easy Wiring

MECHANICAL INSTALLATION

Mounting Position

Mount and calibrate in vertical position for quick and easy installation
on ducts, walls or ceilings and in control rooms.

Media Compatibility

Model 260 transducers are designed to be used with air or
nonconducting gases.

Use with liquids or corrosive gases will damage the unit.

Environment

The operating temperature limits of the 260 are as follows:

Operating Temperature                          32

°

F to 122

°

F (0

°

C to 50

°

C)

Compensated Temperature Range     32

°

F to 122

°

F (0

°

C to 50

°

C)

Model MS1

        0.1”, 0.25”, 0.5” and 1.0” W.C. FS           +/- 0.1”, 0.25”, 0.5” and 1.0” W.C. FS

Model MS2

       1.0”, 2.5”, 5.0” and 10” W.C. FS                +/- 1.0”, 2.5”, 5.0” and 10” W.C. FS

Model MS3

        25, 50, 100 and 250 Pa FS                          +/- 25, 50, 100 and 250 Pa FS

Model MS4

       .25, .50, 1.00 and 2.5 kPa                            +/- .25, .50, 1.00 and 2.5 kPa

                                                                          Ranges

Version                          Unidirectional                                                     Bidirectional

2-Wire

        4-20 mA (Current)

3-Wire

       1-5, 0-5, or 0-10 VDC (Voltage)

 

+

 

+

 +

 +

*Step 2 will follow same
instructions for other inches of
water column and pascal
ranges.

Reviews: