GENERAL

*

Transducer should not be subjected to greater than the maximum allowable pressure or
temperature as defined in the transducer specification.

*

Transducer should not be subjected to mechanical impact.

*

In the event of fire the end user must ensure that the system pressure is vented to a safe
area.

*

The effects of decomposition of unstable fluids should be considered by the user when
placing this device in service.

*

The pressure transducer has no means of draining or venting, this must be performed by
another component in the end users system.

*

Pressure range must be compatible with the maximum pressure being measured.

*

Pressure media must be compatible with the transducer wetted parts which are stainless steel to
UNS 31803, Ceramic and Nitrile

*

Exposed end of cable must be kept free from moisture.

*

Liquid must not be allowed to freeze in the pressure port.

MECHANICAL INSTALLATION

Pressure Connections

:

1)

 

G¼ internal pressure connection to BS2779.  Alternative fitted as specified at time of
order.

2)

 

KF25 Flange

Pressure couplings screwed into G¼ pressure ports should have a maximum thread engagement of 0.5”
(13mm) and 

UNDER NO CIRCUMSTANCES

 be allowed to touch the pressure sensitive

diaphragm.  Pressure couplings should be sealed against the outer face at the pressure port entry using
bonded seal washer such as:-

Part Number

Description

Dowty Ref

GA29

G¼ bonded seal up to +212°F (+100°C) operation

400-021-4490-02

GA30

G¼ bonded seal up to +392°F (+200°C) operation

300-021-0967-02

GA31

G1/8 bonded seal up to +392°F (+200°C) operation

300-020-0967-02

Refer to Dowty for external pressure ratings.

Mounting

: Pressure Transducer is designed to be attached by the coupling thread.  Alternatively units

fitted with an immersible cable can be suspended via the cable or flange.  Omni-directional.  To fit, use a
5/8 UNF AF (M16) wrench on the hexagon provided and apply maximum torque of 20 lbf-ft (27 Nm).
The Customer must ensure that the pressure seal is suitable for the application.  If in doubt contact Setra
Systems.

Effects of Heat

:  Avoid mounting the transducer near a source of heat which is liable to create a

temperature gradient across the instrument.  If this is unavoidable, use a heat shield to deflect uneven
radiated heat or wrap the transducer in glass fibre insulation so that an even temperature is assumed
throughout.

Summary of Contents for 550

Page 1: ...Installation Guide MODEL 550 Low Range Pressure Measuring Transducers 560550 0092 Rev A 1 800 257 3872 TOLL FREE 1 978 264 0292 FAX www Setra com Web Site ...

Page 2: ...Setra offers a complete line of products for these industries Industrial HVAC Test Measurement Barometric Ultra High Purity Sanitary ...

Page 3: ...cer must be accomplished using Setra Systems approved cable see APPROVED CABLE section All instruments conform to the appropriate specifications and or drawings applicable and have been subjected to relevant strict quality control procedures HAZARDOUS PRODUCTS The Consumer Protection Act of 1987 Section 6 of the Heath and Safety at Work Act 1974 and the Control of Substances Hazardous to Health Re...

Page 4: ...ure ports should have a maximum thread engagement of 0 5 13mm and UNDER NO CIRCUMSTANCES be allowed to touch the pressure sensitive diaphragm Pressure couplings should be sealed against the outer face at the pressure port entry using bonded seal washer such as Part Number Description Dowty Ref GA29 G bonded seal up to 212 F 100 C operation 400 021 4490 02 GA30 G bonded seal up to 392 F 200 C opera...

Page 5: ...ved while the system is at pressure Before applying power check that the correct polarity and excitation levels are being applied See ELECTRICAL REQUIREMENTS Cable Version 4 F to 122 F 20 C to 50 C Connector Version 13 F to 185 F 25 C to 85 C Process Media 40 F to 212 F 40 C to 100 C OPERATIONAL LIFE Limited to 10 million full scale cycles CALIBRATION Transducers are calibrated to the range reques...

Page 6: ... Not Used A Y 3 Not Used B Z 4 W C Not Used 5 X D Not Used 6 Y E Not Used 7 Z F Not Used Range Downranging Scope Nominal W 110 to 74 X 78 to 52 Y 54 to 37 Z 47 to 32 LOAD RESISTANCE 4 20mA Transmitter The total permissible resistive load in the loop to include all the cable resistance can be from zero to 50 x supply volts 8 5 ohms e g with a 12V d c supply the permissible load is from zero up to 1...

Page 7: ...CING The transducer cannot be repaired locally and if damaged should be returned to Setra Systems with the following 1 Name and phone number of person to contact 2 Shipping and billing information 3 Full description of malfunction 4 Remove any pressure fittings and plumbing that you may have installed and enclose any required mating electrical connectors and wiring diagrams Please ship prepaid to ...

Page 8: ...emperatures in excess of 400 C CONTACT OUR SALES OR SERVICE DEPARTMENT TO ASCERTAIN IF THE INSTRUMENT CONTAINS VITON W A R N I N G ELECTRICAL CONNECTIONS 4 20MA VOLTAGE IN IN GROUND IN COM OUT GROUND CABLE R BL DRAIN R W Y DRAIN CONNECTOR 1 2 E 1 2 3 E OUTPUT SUPPLY VOLTAGE 4 20mA 9 35V d c 0 5 5 5V d c 7 5 35V d c 1 6V d c 8 35V d c 0 5V d c 7 5 35V d c 0 1 5 1V d c 7 5 35V d c 1 5V d c 7 5 35V d...

Page 9: ......

Reviews: