Chapter D - Setting to work
Rev. A 10-99
DigiDrive Manual Series 2000 / 4000
Pg 70
Servo Dynamics Corp. 21541-D Nordhoff St. Chatsworth, CA 91311 www.servodynamics.com
Display
Trouble shooting
I
2
t reached alarm.
Check Resolver shift angle Parameter (P1).
Check I2t motor Parameter (P5).
Check drive capacity for the application.
Motor thermostat alarm.
Motor overload.
Motor thermal switch disconnected or bad connected.
Check Motor Thermostat n/o or n/c parameter (P2).
Drive internal over temperature alarm (> 80°C).
Drive overloaded.
Drive cooling deficient.
Resolver alarm.
Resolver wiring or link failure.
Resolver failure.
Check resolver type see section 3.7 of chapter A.
Power module fault (over I or over temperature).
Switch off and check motor, look for short circuits between motor
phases.
Over or under voltage alarm
Check main supply input voltage L1, L2 and L3.
Software watchdog.
Check time-out, Watchdog software communication parameter
(P32).
Check serial link.
appears
during 1 second on
display.
Over current alarm (125% of maximum drive current reached).
Bad regulation parameters, refer to « How to set the current loop
parameters » , section 4.2 of chapter D.
Check Power supply voltage, 3 x 230V for 2000 series or 3 x 400V
for 4000 series.
Over speed alarm (125% of max. motor speed reached)
Check Maximum speed (for 10V input) parameter (P23) value.
Motor link fault.
Motor connection failure.
Earth fault.
Look for a possible short circuit between earth and motor phases.