Switched PDU
Installation and Operations Manual
Operations
91
UPS Administration
Creating a UPS record
The Create UPS command adds a new UPS device to the PDU.
To create a UPS record:
At the Switched CDU: prompt, type
create UPS
and press
Enter
.
At the prompt, type the corresponding number from the list of the UPS types and press
Enter
.
At the Host Name: prompt, type the UPS’s IP address or hostname and press
Enter
.
NOTE:
Both IPv4 and IPv6 formats are accepted for IP address or hostname.
Example
The following command creates a UPS record for a Toshiba UPS with the hostname “DC1Toshiba1”:
Switched CDU: create ups<Enter>
UPS types:
1 -- Generic <RFC1628>
2 -- Liebert
3 -- MGE
4 -- Tripp Lite
5 -- APC
6 -- HP
7 -- Minuteman
8 -- Mitsubishi
9 -- Powerware
10 -- Toshiba
11 -- Falcon Electric
Select type(1-11): 10<Enter>
Host/IP: DC1Toshiba1<Enter>
Removing a UPS record:
The Remove UPS command removes a UPS record.
To remove a UPS record:
At the Switched CDU: prompt, type
remove ups
and press
Enter
.
At the prompt, type the index number of the UPS to be removed and press
Enter
.
Example
The following command removes the UPS record at index 3:
Switched CDU: remove ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: Powerware
Host/IP: DC1Powerware1
3 Type: Toshiba
Host/IP: DC1Toshiba1
Select UPS(1-8): 3<Enter>