background image

Model

Available Input

 Voltages

Outlets

Available Input

 Cord

Amperage

Dimensions**

(L x W x D)

© Server Technology, Inc. 10/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.

Sentry :

 Solutions for the Data Center Equipment Cabinet

Key Features

Sentry :

 CDU Technical Specifications

Sentry Switched CDU

CW-24VD/Y

High-Density Power Distribution

The Switched CDU’s combine remote configuration and management 
with power distribution and power and environmental monitoring. 
Reboot a single or dual-power server with one command. Receive 
SNMP-based alerts and email alerts when power or environmental 
conditions exceed thresholds. Assign users specific access rights to 
designated outlets or groups. 

Only the Switched CDU products provide the flexibility needed for all 
data centers and remote sites, including power requirements for 
high-amp, high voltage; UL 60950-1 branch circuit protection; SSL & 
SSH security; and SNMP-based input current monitoring.

The Switched CDU also supports Enterprise View PDU Manager. 
This gives the engineer the ability to manage  a large installation of 
Networked CDUs from one location, view and access multiple Smart 
and Switched CDUs from a 

single web interface. 

> Remote Power Management:

 

Power cycle individual power 

outlets, or groups of power 

outlets, to remotely reboot 

servers and network devices, 

anywhere in the world.  Or, 

power-off unused power 

receptacles

> High Power Distribution

3-Phase power; 20 or 30-Amp 

power input feed options 

> High Density: 

 Single power 

input feed; 24 outlets per 

enclosure

> IP Access & Security: 

 Web 

interface, SSL, SSH, Telnet, SNMP, 
FTP, SNTP, Syslog, LDAP, LDAPS, 
TACACS

 

and RS-232 access

> Add an Expansion Module: 

 

Daisy chain the Switched CDU 

Expansion Module (CW/CX) for 

power management of separate 

power circuits from a single IP 

address  

> Environmental Monitoring: 

 

Each Switched CDU supports two 

temperature & humidity probes 

and reports conditions thru the 

Web interface

> Enterprise View: 

 View and 

access multiple Switched CDUs 

from one Web interface**

> SNMP Traps: 

Provide automated 

alerts for power and 

environmental conditions

> Input Current Monitor:

 

Precisely measure the aggregate 

current draw (in amps) on each 

power circuit.  On-site verification 

of the input current with the LED 

digital display.  Remote 

verification via browser or serial 

screen.

Power-up Sequencing:

 Prevent 

an in-rush power overload

 

Branch Circuit Protection

The Sentry CDU Family meets the new UL 60950-1 
requirement for branch circuit protection.  

Attention!

 

The Sentry CDU products meet the above criteria by 

providing overcurrent protection with UL-listed Bussman SC fuses for  
each branch circuit. 

Input Current Monitoring

 

The CDU’s exclusive True RMS current monitoring is critical 
to preventing overloads in high-density computing  
environments.  LED digital displays on the CDU enclosure 
report the input current of each phase or branch circuit.

              

Temperature and Humidity 

   

 

 

The Switched CDU supports two external probes. Each of 
these probes measure both temperature and humidity.  
Receive SNMP-based alert notifications when conditions 
exceed defined thresholds.

              

Additional Benefits:

CW-24V2-C20M

CW-24VY-L20M*

CW-24V2-L30M

CW-24VY-L30M*

208-240V

50/60Hz

208-240V

50/60Hz

3-Phase Wye, 208V

50/60Hz

3-Phase Wye, 208V

50/60Hz

30A

20A

30A

20A

IEC 60320/C20

Power Inlet

NEMA L6-30P

Cordset

NEMA L21-20P

Cordset

NEMA L21-30P

Cordset

(24) IEC 60320/C13*

(24) IEC 60320/C13*

69.0” x 1.75” x 2.25”

69.0” x 1.75” x 2.25”

69.0” x 1.75” x 2.25”

69.0” x 1.75” x 2.25”

Additional Features and Specifications

Branch Circuit Protection

> Compliant to UL 60950-1

Agency Approvals

> US & Canada (cTUVus mark) to UL 60950-1:2003 and               

   CAN/CSA 22.2 No. 60950-1-03 

        

> European Union (TUVGS mark) to EN 60950-1:2001  

> FCC Class A, Part 15 

    

> CE

> EMC - EN 55022 Class A, EN 55024

Communications and Security

> 10/100 BaseT Ethernet 

        

> HTTP/HTTPS  

        

> SSLv3/TLSv1  

       

> SNMPv2   

 

        

> SSHv2

> Telnet

> LDAPv3

> LDAPS

> RS-232 (Serial)

Accessories

> Optional Temperature & Humidity Probe

 

EMTH-1-1 Temperature & Humidity Probe, 10’

 

Power Cord Options

> PTCORD-1       IEC 60320/C19 - NEMA L6-20P , 10’

> PTCORD-2       IEC 60320/C19 - Schuko 10’ 

> PTCORD-3       IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 

                            16/20A Blue (UK Commando) 10’

> PTCORD-4       IEC 60320/C19 - BS1363 13A (UK) 10’

> PT-ADP-C19    Cable mount IEC 60320/C19 Connector

**Enterprise View sold separtely

Expansion Module 
Model Numbers

> CX-24VD-L20M
> CX-24VD-L30M
> CX-24VY-L20M
> CX-24VY-L30M

(24) IEC 60320/C13

(24) IEC 60320/C13

CW-24VE-C20M

CW-24VE-P32M

230V

50/60Hz

230V

50/60Hz

32A

16A

IEC 60320/C20

Power Inlet

IEC 60309

Cordset

69.0” x 1.75” x 2.25”

69.0” x 1.75” x 2.25”

(24) IEC 60320/C13

(24) IEC 60320/C13

*This unit has an additional NEMA 5-20R, 110V Utility Outlet
**Please note that the depth of these enclosures are 3.0” deep at the placement of the fuse retractors

CW-24VD-L20M

CW-24VD-L30M

3-Phase Delta, 208V

50/60Hz

3-Phase Delta, 208V

50/60Hz

30A

20A

NEMA L15-20P

Cordset

NEMA L15-30P

Cordset

(24) IEC 60320/C13

(24) IEC 60320/C13

69.0” x 1.75” x 2.25”

69.0” x 1.75” x 2.25”

Ex
M