WIRING AND CONNECTIONS

Wiring diagram 

RJ45 sockets  (Power over Modbus) 

Pin 1

24 VDC

Supply voltage 

Pin 2 
Pin 3

A

Modbus RTU communication, signal A

Pin 4
Pin 5

/B

Modbus RTU communication, signal /B

Pin 6
Pin 7

GND

Ground, supply voltage

Pin 8

/B

A

GND

24 VDC

8 mm

8 mm

8 mm

8 mm

RJ45

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

3

4

5

6

3

4

Terminal Block 1

VIN

Supply voltage 24 VDC

GND

Supply voltage, ground 

A

Modbus RTU communication, signal A 

/B

Modbus RTU communication, signal /B

Terminal Block 2

AO1

Analogue / modulating output 1 for temperature 

measurement  (0—10 VDC / 0—20 mA / PWM)

GND

Ground AO1

AO2

Analogue / modulating output 2 for relative humidity 

measurement (0—10 VDC / 0—20 mA / PWM)

GND

Ground AO2

AO3

Analogue / modulating output 3 for CO / NO

2

 measurement 

(0—10 VDC / 0—20 mA / PWM)

GND

Ground AO3

ATTENTION

The unit needs to be supplied via the RJ45 connector or via the connection 
terminals. Do not connect the device via the RJ45 connector and the terminal 
block simultaneously!

 

ATTENTION

This product is not suited for 3-wire connection. It has separate grounds for power 
supply and analogue output. Connecting both grounds together might result in 
incorrect measurements.

 MOUNTING & OPERATING INSTRUCTIONS IN STEPS 

Before you start mounting the unit, read carefully 

“Safety and Precautions”

Choose a smooth surface for installation (a wall, panel and etc.).

ATTENTION

When planning the installation, allow enough clearance for maintenance and 
service. Mount the sensor in a well-ventilated area.

RSCOH-R

MULTIFUNCTIONAL 
ROOM TRANSMITTER 

Summary of Contents for RSCOH-R

Page 1: ...Mounting and operating instructions RSCOH R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Page 2: ...ES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 9 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 TRANSPORT AND STORAGE 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 RSCOH R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Page 3: ...environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connect...

Page 4: ...min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 30 70 C Selectable relative humidity range 0 100 Selectable CO range 0 1 000 ppm Replaceable CO NO2 sensor element 3 LEDs with adjustable light intensity for status indication Accuracy 0 4 C 0 50 C 3 rH 0 100 rH Enclosure rear plate plastic ABS black RAL 9004 front cover ASA ivory RAL 9010 Protection standard IP30...

Page 5: ...93 to EN 60529 EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 General requirements WEEE 2012 19 EC RoHs Directive 2011 65 EC OPERATIONAL DIAGRAMS 10 0 50 20 30 40 50 60 70 80 90 100 Minimum range Minimum alert Maximum alert Analogue modulating outputs T C Maximum range Out of range Within range Alert range Alert range Out of range LED indications T default rH or...

Page 6: ...2 for relative humidity measurement 0 10 VDC 0 20 mA PWM GND Ground AO2 AO3 Analogue modulating output 3 for CO NO2 measurement 0 10 VDC 0 20 mA PWM GND Ground AO3 ATTENTION The unit needs to be supplied via the RJ45 connector or via the connection terminals Do not connect the device via the RJ45 connector and the terminal block simultaneously ATTENTION This product is not suited for 3 wire connec...

Page 7: ...able fastening materials not supplied position the room sensor at least 1 5 m from the floor When planning the installation allow enough clearance for maintenance and service Mount the sensor in a well ventilated area Mind the correct mounting position and unit dimensions See Fig 2 and Fig 3 Fig 1 Snap fits release Fig 2 Mounting dimension Push here to release 2 x Ø 6 59 8 9 8 74 5 104 5 20 104 5 ...

Page 8: ...stant if necessary For the default factory setting refer to the product Modbus register map For the complete Modbus register data refer to the product Modbus Register Map which is a separate document attached to the article code on the website and contains the registers list Products with earlier firmware versions may not be compatible with this list NOTE 5 5 Optional settings To assure correct co...

Page 9: ...ality the unit firmware can be updated via Modbus RTU communication With 3SM boot Application part of 3SM center software suite boot mode is automatically activated and the firmware can be updated NOTE Make sure the power supply does not get interrupted during bootload procedure otherwise you risk losing unsaved data LED indications 1 When the green LED is on the measured value temperature relativ...

Page 10: ...TALLATION INSTRUCTIONS After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the prod...