www.sentera.eu

MIW-STR-1100-1200-LXX-EN-000 - 09 / 08 / 2018

5 - 8

back to the table of contents

OPERATIONAL DIAGRAM

Operational diagram - L22

Operational diagram - L20

Regulated output

 (U)

Unregulated output

 (L1)

Knob 

position

0

1

2

3

4

5

230

190

170

140

110

U [VAC]

L1

Knob 

position

0

1

2

3

4

5

230

170

140

120

100

U [VAC]

L1

Regulated output

 (U)

Unregulated output

 (L1)

WIRING AND CONNECTIONS

Connections

L

Power supply, line (230 VAC / 50—60 Hz)

N

Power supply, neutral

L1

Unregulated output, line

N

Regulated output to motor, neutral

U

Regulated output to motor, line

Earth terminals

ATTENTION

Make sure you use cables with an appropriate diameter.

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the STR-1, read carefully 

Safety and Precautions”

 and 

follow these steps. Choose a smooth solid surface for installation (a wall, panel, etc.).

Follow these steps:

1. 

 Open the door of the controller. Mind the wires that connect the rotary switch 
with the autotransformer or with the printed circuit board, depending on the 
product version. 

2. 

 Mount the enclosure using corrosion resistant screws or bolts.  Mind the correct 
mounting position and unit mounting dimensions (see 

Fig. 1

 

Mounting dimensions 

and 

Fig. 2

 

Mounting position

). The mounting holes are on the inside back panel of 

the enclosure and are covered with blanking plugs. 

3. 

 Pay attention to following instructions in order to minimize the operating 

temperature:

3.1 

 Respect the distances both between the wall /ceiling and the device and 
between  two devices as shown in 

Fig. 2. 

In order to ensure sufficient 

ventilation of the controller, clearance on every side has to be maintained.

STANDARD 230 VAC 
TRANSFORMER CONTROLLER

STR-1

Summary of Contents for STR-1

Page 1: ...Mounting and operating instructions STANDARD 230 VAC TRANSFORMER CONTROLLER POWER RANGE 10 0 20 0 A STR 1 ...

Page 2: ...UCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 STANDARD 230 VAC TRANSFORMER CONTROLLER STR 1 ...

Page 3: ...ironment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting...

Page 4: ...STR 1160L20 16 0 F T 25 0 A H STR 1200L20 20 0 F T 30 0 A H INTENDED AREA OF USE Speed control of voltage controllable 230 VAC single phase motors For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current depends on the version see article codes Unregulated output 230 VAC Wide power range 5 step rotary switch for manual control plus off position LED status indication...

Page 5: ...ions and follow these steps Choose a smooth solid surface for installation a wall panel etc Follow these steps 1 Open the door of the controller Mind the wires that connect the rotary switch with the autotransformer or with the printed circuit board depending on the product version 2 Mount the enclosure using corrosion resistant screws or bolts Mind the correct mounting position and unit mounting ...

Page 6: ...Incorrect 50 mm 50 mm 75 mm 50 mm 1 3 2 4 Article code A mm B mm C mm D mm E mm STR 1100L22 300 325 185 255 255 STR 1130L22 300 325 185 255 255 STR 1160L20 300 425 235 255 355 STR 1200L20 300 430 235 255 355 6 Insert the cables through the cable glands and do the wiring according to the wiring diagram see Fig 3 while adhering to the information from section Wiring and connections above 6 1 Connect...

Page 7: ...0 110 140 170 190 230 Unregulated output VAC L1 0 230 230 230 230 230 230 Available but not connected VERIFICATION OF INSTALLATION ATTENTION Use only tools and equipment with non conducting handles when working on electrical devices After connecting the unit to the mains supply the green LED on its cover should light up indicating that the controller is supplied Safe operation depends on proper in...

Page 8: ... alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should ...