www.sentera.eu
MIW-RDCV-EN-002 - 27 / 04 / 2017
14 - 17
7-SEGMENT DISPLAY INDICATION
Indication
Description
Digits
Output value, menu items and settings
A decimal point
Stand-by mode
Blinking digits
Parameter saving or unit reset
1—100
Output value in working mode
Digits a with a point
Parameter value in setting mode
Indication of output steps
Toggled with output value by pressing
MODBUS REGISTER MAPS
INPUT REGISTERS (Read-only)
Data type
Description
Data
Values
30001
Output value
unsigned int.
Output value in %
0—100
100 =
50 =
10,00 VDC / 20,00 mA / 100 % PWM
5,00 VDC / 10,00 mA / 50 % PWM
30002
Output step
unsigned int.
Current output step, when a step is set greater then ‘0’
0—9
0 =
1 =
First step
Second step
30003
Output mode
unsigned int.
Output mode: Voltage / Current / PWM
0—2
0 =
1 =
2 =
0—10 VDC
0—20 mA
PWM
30004
Minimum output value
unsigned int.
Minimum value of output signal
0—80
20 =
2 VDC / 4 mA / 20 % PWM
30005
Maximum output value
unsigned int.
Maximum value of output signal
40—100
80 =
8 VDC / 16 mA / 80 % PWM
30006-
30007
Reserved, return “0”
30008
Overwrite mode
unsigned int.
Manual / overwrite mode
0—1
0 =
1 =
Manual mode
Overwrite mode
30009-
30010
Reserved, return “0”
Note:
The input registers can be read via the Modbus command: “Read input registers”.
RDCV
RESIDENTIAL HVAC
CONTROLLER