ATTENTION
G and F-types devices cannot be used together in the same network. G and
F-type devices must be supplied by separate power supplies. Do not connect the
GND terminals of G and F-type devices together.
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the HPS-X-2 differential pressure transmitter, read
carefully
“
Safety and Precautions”
. Choose a smooth surface for an installation
location (a wall, panel, etc.) and follow these steps:
1.
Unscrew the front cover of the enclosure to remove it.
2.
Fix the enclosure onto the surface by means of suitable fasteners while adhering
to the mounting dimensions shown in
Fig. 1
Mounting dimensions
and the correct
mounting position shown in
Fig. 2
Mounting position
.
Fig. 1 Mounting dimensions
Fig. 2 Mounting position
2x Ø 3,4
49
52
Acceptable
Not acceptable
HPS
+ _
HPS
+
_
HPS
+
_
3.
Insert the cable though the grommet.
4.
Connect as shown in
Fig. 3
Connections
adhering to the information in section
“
Wiring and connections
”.
Fig. 3 Connections
Power supply
G: 15—24 VAC ± 10% /
18—34 VDC
F: 18—34 VDC
Modbus RTU
A /B
Analogue / digital (PWM) output
0—10 VDC / 0—20 mA
5.
Connect the nozzles with the tubing.
6.
Put back the front cover and fix it.
7.
Switch on the power supply.
DIFFERENTIAL PRESSURE
TRANSMITTER
HPS-X -2