PRODUCT DESCRIPTION

The HPD series are compact high resolution double differential pressure transmitters, 
which are equipped with two fully digital pressure transducer designed for a wide 
range of applications. Air velocity readout is available by connecting an external 
Pitot tube connection set. All parameters are accessible via Modbus RTU (3SModbus 
software or Sensistant). They also feature integrated K-factor and 2 analogue / 
modulating outputs (0—10 VDC / 0—20 mA / 0—100 % PWM).

ARTICLE CODES

Codes

Power supply 

Maximum power 

consumption

Nominal power 

consumption

Imax

Operating range

HPD-F-1K0

18—34 VDC

1,85 W

1,35 W

100 mA

0—1.000 Pa

HPD-F-2K0

0—2.000 Pa

HPD-F-4K0

0—4.000 Pa

HPD-F-10K

0—10.000 Pa

HPD-G-1K0

18—34 VDC  /

1,85 W

1,35 W

105 mA

0—1.000 Pa

HPD-G-2K0

0—2.000 Pa

HPD-G-4K0

15—24 VAC ±10 %

3,4 W

2,5 W

230 mA

0—4.000 Pa

HPD-G-10K

0—10.000 Pa

INTENDED AREA OF USE

 

Differential pressure measurement in HVAC applications

 

Volume flow measurement in HVAC applications

 

 

Air velocity measurement (by using an external PSET-PTX-200 Pitot tube 

 

connection set) in HVAC applications

 

Differential pressure / volume flow monitoring in clean rooms

 

Clean air and non-aggressive, non-combustible gases 

TECHNICAL DATA

 

2 built-in digital high resolution differential pressure sensors

 

 Air velocity can be measured via Modbus RTU (by using an external PSET-PTX-200 
Pitot tube connection set)

 

 2 selectable analogue / modulating outputs: 0—10 VDC / 0—20 mA / PWM (open 
collector type): 

 

0—10 VDC mode: R

L

 ≥ 50 kΩ

 

0—20 mA mode: R

L

 ≤ 500 Ω

 

PWM mode: PWM Frequency: 1 kHz, R

L

 ≥ 50 kΩ

 

Minimum differential pressure range span: 5 Pa

 

Minimum volume flow range span:  10 m

3

/h

 

Minimum air velocity range span: 1 m/s

 

Selectable response time: 0,1—10 s

 

Implemented K-factor

 

Selectable internal voltage source for PWM output: 3,3 or 12 VDC 

 

Differential pressure, air volume or air velocity readout via Modbus RTU

 

 Selectable minimum and maximum operating ranges

 

Modbus registers reset function (to factory pre-set values)

 

Modbus RTU communication

 

Sensor calibration procedure via tact switch

 

Aluminium pressure connection nozzles

 

Accuracy: ±2 % of the operating range

 

Operating ambient conditions:

 

Temperature: -5—65 °C

 

Rel. humidity: < 95 % rH (non-condensing)

 

Storage temperature: -20—70 °C

DUAL DIFFERENTIAL 
PRESSURE TRANSMITTER 

HPD

Summary of Contents for HPD

Page 1: ...Mounting and operating instructions HPD DUAL DIFFERENTIAL PRESSURE TRANSMITTER ...

Page 2: ...ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 OPERATING INSTRUCTIONS 9 TRANSPORT AND STORAGE 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 DUAL DIFFERENTIAL PRESSURE TRANSMITTER HPD ...

Page 3: ...e work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before ...

Page 4: ...nt by using an external PSET PTX 200 Pitot tube connection set in HVAC applications Differential pressure volume flow monitoring in clean rooms Clean air and non aggressive non combustible gases TECHNICAL DATA 2 built in digital high resolution differential pressure sensors Air velocity can be measured via Modbus RTU by using an external PSET PTX 200 Pitot tube connection set 2 selectable analogue...

Page 5: ...ective 2012 19 EC RoHs Directive 2011 65 EC OPERATIONAL DIAGRAM 0 10 20 30 40 50 60 70 80 90 100 10 20 30 40 50 60 70 80 90 100 VDC mA PWM Output Differential Pressure Range Pa Control range Minimum Control range Maximum WIRING AND CONNECTIONS Article type HPD F HPD G Vin 18 34 VDC 18 34 VDC 13 26 VAC Ground Common ground AC GND Ground AC A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B AO1...

Page 6: ...oose a smooth surface for installation a wall panel etc and follow these steps 1 Unscrew the front cover of the enclosure to remove it 2 Fix the enclosure onto the surface by means of suitable fasteners while adhering to the mounting dimensions shown in Fig 1 and the correct mounting position shown in Fig 2 below Fig 1 Mounting dimensions Fig 2 Mounting position HPD _ 80 65 85 2x Ø 6 46 24 20 15 1...

Page 7: ...led and Pitot tube connected 6 3 To measure air velocity use PSET PT set and enable Pitot tube air velocity via holding register 64 for sensor module 1 or in holding register 84 for sensor module 2 In this case the K factor of the fan has to be 0 Fig 4 Connecting with accessories Application 1 Measuring differential pressure Pa or volume flow m h using PSET PVC Application 2 Measuring volume flow ...

Page 8: ... Example 1 Example 2 RX ТX NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n NOTE On a Modbus RTU network two bus terminators NBTs need to be activated 9 Put back the front cover and secure it with the screws 10 Customise the factory settings to the desired ones via the 3SModbus software or the Sensistant configurator For the default factory settings see Modbus re...

Page 9: ... indication 1 3 After the calibration is done the blue LED3 will blink twice once again to indicate that the calibration procedure has finished 2 Sensor module 2 2 1 Disconnect the nozzles and make sure they are not clogged 2 2 There are two options for starting the calibration process Either write 1 in holding register 90 or press tact switch SW2 for about 5 seconds until the blue LED4 on the pri...

Page 10: ...ditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance fr...