WSX 2P
FAMILY
INSTRUCTIONS
WSX 2P
WSX PDT 2P
WSX 2P NL
WSX PDT 2P NL
PHYSICAL SPECS
SIZE: 2.74”H x 1.68”W x 1.63”D (6.96 cm x 4.27 cm x 4.14 cm)
(not including ground strap)
WEIGHT: 5 oz
MOUNTING: Single Gang Switch Box
MOUNTING HEIGHT: 30-48 in (76.2-121.9 cm)
SILICONE FREE
ROHS COMPLIANT
ELECTRICAL SPECS
MAXIMUM LOAD / POLE (RELAY)
800 W @ 120 VAC
1200 W @ 277 VAC
1500 W @ 347 VAC
MINIMUM LOAD: None
MOTOR LOAD: 1/4 HP
FREQUENCY: 50/60 Hz (timers are 1.2x for 50 Hz)
ENVIRONMENTAL SPECS
OPERATING TEMP
Standard: 14º to 122º F (-10º to 50º C)
LT Option (PIR): -40º to 122º F (-40º to 50º C)
LT Option (PDT): -4º to 122º F (-20º to 50º C)
RELATIVE HUMIDITY:
Standard: 20 to 75% non-condensing
LT Option: 20 to 90% non-condensing
(electronics coated for corrosion resistance)
SPECIFICATIONS
COVERAGE PATTERN
36 30 20 10 0 ft 10 20 30 36
12 9 6 3 0 m 3 6 9 12
Small
motion
detection
Small
motion
detection
to ~20 ft
6
3
0 m
20
10
0 ft
Small motion ~40 ft coverage
TOP V I EW
1.2 m
4 ft
Small motion
detection to ~20 ft
Large motion detection to >36 ft
SI DE V I EW
0
18
27
36
9
ft
0
6
9
12
3
m
This product is
pre-configured for wiring without a neutral; however, if connection to neutral is required by code, contractors can quickly and easily convert the unit in seconds.
CONVERSION FROM GROUND ONLY (NO NEUTRAL) TO NEUTRAL WIRING
Step 1:
Remove Yellow
Label
Step 2:
Loosen Screws and
Remove Metal Link
Step 3:
Connect Neutral to
Silver Screw and
Ground to Green Screw
WIRING TO GROUND (NO NEUTRAL)
WIRING TO NEUTRAL
H
N
GND
LOAD 2
BLU
BLU
H
N
LOAD 1
BLK
BLK
REMOVE MET
AL LINK
IF CONNECTING T
O
NEUTRAL
GND
H
N
LOAD 1
BLK
BLK
N
H
N
LOAD 2
BLU
BLU
DUAL RELAY
DUAL RELAY
Notes:
- Unit will draw power from either line connection.
- When switching 277 VAC or 347 VAC on both relays, the
line inputs must be of the same phase.
120/277 VAC WIRING
BLACK*
- Line 1 Input
BLACK*
- Load 1 Output
*BLACK wires
can be reversed
}
BLUE*
- Line 2 Input
BLUE*
- Load 2 Output
*BLUE wires
can be reversed
}
WI RE COLOR K EY
347 VAC WIRING (-347 Option)
Red wires replace Black wires.
Notes:
- Unit will draw power from either line connection.
- When switching 277 VAC or 347 VAC on both relays, the
line inputs must be of the same phase.
•
Small motion (e.g. hand movements) detection up to 20 ft (6.10 m), ~625 ft
2
•
Large motion (e.g. walking) detection greater than 36 ft (10.97 m), ~2025 ft
2
•
Wall-to-wall PIR coverage
•
Units with -PDT (Passive Dual Technology) option
(also called Microphonics) provide overlapping
detection of human activity over the complete
PIR coverage area. Advanced filtering is utilized
to prevent non-occupant noises from keeping
the lights on.