Chapter 6: PowerGate2
107
Tabletop Installation
The IMS-4302 PowerGate2 can be installed on a tabletop or shelf. Follow the steps below:
1) Attach the four self-adhesive rubber feet to the four corners on the bottom of the IMS-4302.
2) Place the unit on a tabletop or shelf and connect the power cord into a 120VAC outlet.
Figure 4: Tabletop-mounted PowerGate2 Unit
Connection to IMS-4000 Host or Node
The PowerGate2 connects to an IMS-4000 Host or Node using the 9-pin null modem cable (includ
-
ed). Connect the cable to the RS-232 port on the PowerGate2 and connect the other end to the RS-
232 port on the Host or Node. The PowerGate2 will automatically be recognized by the system and
appear in the IMS-4000 ConsoleView software.
Figure 5: PowerGate2 to Node connection
Operation
The PowerGate2 switches power from each power input on the front of the unit to the correspond
-
ing outlet on the back (e.g., power input 1 goes to outlet 1). Each PowerGate2 circuit can switch up
to 12A of current. Be sure the power source can supply the current required for your equipment.
Do not connect several power inputs to one 15A circuit and then try to turn on several high-current
devices, as this will surely trip a breaker in your electric service panel.