SENS EnerGenius® DC Compact Technical Manual
12
5
MOUNTING INSTRUCTIONS
INSTALLATION OF THE UNIT MUST COMPLY WITH LOCAL ELECTRICAL CODES AND OTHER APPLICABLE
INSTALLATION CODES AND BE MADE ACCORDING TO THE INSTALLATION INSTRUCTIONS AND ALL
APPLICABLE SAFETY REGULATIONS.
Printed circuit boards contain static sensitive components. Damage can occur even when static levels are too
low to produce a noticeable discharge shock. To avoid static discharge damage, handle the charger by the
chassis only. Remove the cover only when access is essential for installation and service and replace it
promptly when finished.
5.1.
Mounting Location
See diagrams at back of manual for dimensions and mounting information.
5.1.1.
Charger is rated IP20.
5.1.2.
Charger will operate at full specification when located where temperatures are within -40°C
(-40°F) to +50°C (122°F). Output power is gradually reduced at higher temperatures.
5.1.3.
Leave clear space for ventilation all around the charger: at least 6 inches (15 cm) at the top; at
least 4 inches (10.16 cm) at the bottom; at least 0.5 inches (1.27 cm) on each side. Operating
temperature ranges stated above assume stated clearances.
5.1.4.
Mount to a wall or other vertical support. The mounting surface must safely support the weight of
the charger and the fixed wiring. Charger weighs 43 lbs (19.5 Kg).
5.1.5.
Allow sufficient room for routing the fixed wiring to the charger. All field connections enter the
charger from the side. See diagrams at back of manual for further information.
5.1.6.
Do not mount the charger above any heat generating equipment or where it could get wet.
5.2.
Mounting Instructions
5.2.1.
Drill four wall mounting holes using dimensions provided on diagrams at back of manual.
IMPORTANT: Protect charger from all drill shavings!
5.2.2.
Mount the charger before connecting AC, DC, communications and alarm wiring to ensure un-
obstructed access to mounting holes.
5.2.3.
Mount the charger using four ¼ inch (M6) screws with standard flat washers. Mounting hardware