CONFIGURATION OF THE RS485 PORT BY DIP SWITCH
The SW1 dip switch is used to configure the parameters related to the RS485 communication port.
DIP switches 1 and 2 are used for the baud rate of the RS485 port
DIP switches 3 to 8 are used for the Modbus station address of the RS485 port
ATTENTION!
The configuration via dip switch is active only after a restart!
ATTENTION!
The configuration via dip switch has priority over the one saved in flash, if you need to use the
configuration of the RS485 port sent by Easy Setup you must bring all the dip switches 1..8 to "OFF"
and restart the device.
CONFIGURATION OF THE FLASH MEMORY RS485 PORT
If ALL the dip switches 1 ... 8 are OFF, the device uses the configuration saved in Flash (configured with the
Easy Setup software) for the RS485 port.
RS485
configuration
DIP1
DIP2
DIP3
DIP4
DIP5
DIP6
DIP7
DIP8
FROM
FLASH
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF