background image

 

          

MI00369-3-EN 

ENGLISH6/8

 

Factor IP address 

The default module IP address is static: 192.168.90.101 

Web Server 

To access the maintenance Web Server with 192.168.90.101 factory IP address 
(Default user: admin; Default password: admin) 

http://192.168.90.101/maintenance/index.html

  

To access the custom Web Server on SD card with 192.168.90.101 default IP address 

http://192.168.90.101/index.html

 

 

SW1 DIP-switch settings to upload factory settings 

This procedure restores the IP address to factory settings: 192.168.90.101 and 
Webserver/FTP server user login credentials: admin and password: admin. 

KEY 

Turn off the Z-KEY module and set all eight SW1 DIP-switches 

ON

Turn on the Z-KEY module and wait 10 seconds. 
Turn off the Z-KEY module and set all eight SW1 DIP-switches 

OFF

ON 



OFF 

 

SW2 DIP-switch settings 

RS232 or RS485 settings on terminals 10-11-12 (serial port 2) 

KEY 

RS232 

ON 



RS485 

OFF 

 

 

7 INDICATIONS VIA LED ON FRONT PANEL 

LED 

STATUS 

LED meaning 

TX1 (Red) 

Flashing 

Data transmission on port #1 RS485 

RX1 (Red) 

Flashing 

Data receipt on port #1 RS485 

TX2 (Red) 

Flashing 

Data transmission on port #2 RS485 

RX2 (Red) 

Flashing 

Data receipt on port #2 RS485 

PWR (Green) 

On 

Device powered 

SD (Red) 

Flashing 

Access to micro SD card. 

ETH ACT (Green) 

Flashing 

Packet transmission on Ethernet port 

ETH ACT (Green) 

On 

No activity on Ethernet port 

ETH LNK (Yellow) 

On 

Ethernet port connected 

ETH LNK (Yellow) 

Off 

No Ethernet connection 

 

8 ACCESSORIES 

CODE 

DESCRIPTION 

Z-PC-DINAL2-17.5 

Support with power terminal 2 slots pitch 0 1705 mm 

Z-PC-DIN1-35 

1 slot support for rear connector pitch = 35 mm 

Z-PC-DIN4-35 

4 slot support for rear connector pitch = 35 mm 

CE-RJ45-RJ45-R  

1.5 m Ethernet cable 

CS-DB9M-MEF-1012 

Z-KEY / RS232-DB9 serial connection cable 

KIT-USB 

Programming KIT (USB + CD cable) 

MICRO-SD 4GB-MP 

4GN Micro-SD Flash card 

 

 

Summary of Contents for Z-KEY

Page 1: ...ca srl Registered offices Via Austria 26 35127 Z I Padua IT Tel 39 049 8705355 8705355 Fax 39 049 8706287 Website www seneca it Mail Technical support support seneca it Product information sales seneca it This document is property of SENECA srl Copies and reproduction are prohibited unless authorised The content of this document corresponds to the described products and technologies Indicated data...

Page 2: ...rver and FTP server pages One Ethernet 100 Mbits s port One RS485 port One RS485 RS232 commutable port One USB port 1500 V power insulation with respect to the remaining low voltage circuits Facilitated power and serial line cabling via Seneca bus that can be housed in the IEC EN 60715 omega guide Pull out terminals section 2 5 mm2 Power indication RS485 RS232 Rx and Tx ETHERNET connection and act...

Page 3: ...ave protocol RS485 IDC10 rear connector Maximum Baud rate 115k Modbus RTU master Modbus RTU slave protocol RJ45 Ethernet connector on front 100 Mbit s Max distance 100 m with auto switch USB Plug in lateral micro USB Power supply Voltage 11 40 V 19 28 V 50 60 Hz Consumption Typical 1 5W 24 V Max 2 W 24 V Operating conditions Temperature 25 C 50 C Humidity 30 90 to 40 C non condensing Altitude up t...

Page 4: ... the two hooks on the side of the IDC10 rear connector as illustrated in fig 1a Removal from IEC EN 60715 DIN guide As illustrated in figure 1b 1 Move the two side hooks outward from the module assisted by a screwdriver 2 Extract the module from the guide 6 ELECTRICAL CONNECTIONS IDC10 rear connector POWER AND PORT 1 The illustration indicates the meanings of the various IDC10 connector pins if si...

Page 5: ... indication of the RS485 connection polarity is not standardised and in some devices may be inverted Serial port 2 RS485 SW2 ON Z KEY has a serial port that can be set with the SW2 switch If the SW2 switch is ON then terminals 10 11 12 have the RS232 COM 2 available The illustration shows how to complete connections The RS232 interface is fully settable RJ45 Ethernet connector on front Z KEY has a...

Page 6: ...ngs RS232 or RS485 settings on terminals 10 11 12 serial port 2 KEY RS232 ON RS485 OFF 7 INDICATIONS VIA LED ON FRONT PANEL LED STATUS LED meaning TX1 Red Flashing Data transmission on port 1 RS485 RX1 Red Flashing Data receipt on port 1 RS485 TX2 Red Flashing Data transmission on port 2 RS485 RX2 Red Flashing Data receipt on port 2 RS485 PWR Green On Device powered SD Red Flashing Access to micro...

Page 7: ...Material recycling will contribute to the preservation of natural resources To receive further information please contact your local waste disposal service centre or product dealer Z KEY can be fully set up via integrated web server Product programming tools can be downloaded free of charge at www seneca it in the Z KEY section To access settings open the maintenance page in a browser at the Z KEY...

Page 8: ...MI00369 3 EN ENGLISH8 8 ...