background image

USER MANUAL 

 Z-GPRS3, Z-UMTS, Z-LOGGER3, Z-LTE-WW 

 
 

 

 

13

 

 

 

 

To increase the GSM signal level, Seneca provides various GSM antenna models to reach the 
minimum signal level in most situations.  

Visi

www.seneca.it

refer to the general catalogue or contact Seneca srl for further information. 

CAUTION! 

-Insert the SIM card only with RTU off. 

-Before inserting the SIM card, delete all SMS on the SIM using a mobile phone 

-Wait at least 5 minutes in order for the GSM signal to be correctly read. 

CAUTION! 

-Contact your telephone service provider for GSM and GPRS service costs especially when using the 
RTU with a sim issued by a country other than the one in which it is used (international roaming). 

6.

 

INTERNAL UPS 

 

The RTUs are equipped with rechargeable battery.   

In the event of a blackout the board can be configured for: 

 

A)  Will work for up to 1h without external power. 

When the voltage batteries are not sufficient RTU will runs the following algorithm: 

1)

 

End sending data 

2)

 

Close all files opened on microSD 

3)

 

Turn off 

 

B)  It will shutdown without external power. 

 

C)  Without external power the board will send log data and then shutdown 

 

In SEAL this behavior can be decided in System Configuration 

 

Summary of Contents for Z-GPRS3

Page 1: ...ntation refers to products and technologies described in it Though we strive for reach perfection continually all technical data contained in this document may be modified or added due to technical an...

Page 2: ...Changes 05 03 2020 1 18 Fix GNSS Z LTE WW info 21 06 2021 25 Corrected ModBUS register table 05 07 2021 26 Proofreading English texts Added frequency bands for SIM7600G modem 10 01 2022 28 Aggiunti co...

Page 3: ...SMS COMMAND USING PASSWORD ONLY Z GPRS3 Z UMTS Z LTE Z LTE WW 14 7 2 MICROSD CARD PHONE BOOK ONLY Z GPRS3 Z UMTS Z LTE Z LTE WW 15 8 ACQUIRING AND SENDING LOG DATA 15 8 1 THE EVENT LOGGER 16 8 1 1 Sen...

Page 4: ...update by microSD card 32 16 SEAL PROGRAM AND SEAL CONFIGURATION REMOTE UPDATE 33 16 1 SEAL PROGRAM AND SEAL CONFIGURATION UPDATE FROM WEBSERVER 33 16 2 UPLOAD A PROJECT BACKUP TO THE RTU 34 17 MODBUS...

Page 5: ...USER MANUAL Z GPRS3 Z UMTS Z LOGGER3 Z LTE WW 5 21 EMERGENCY MODE 51 22 Z GPRS3 POWER ESTIMATE FOR USE WITH SOLAR PANELS 52 23 TROUBLESHOOTING 52...

Page 6: ...ISTRIBUTORS AND SENECA DEALERS DO NOT GUARANTEE THAT THE FUNCTIONS FAITHFULLY MEET THE EXPECTATIONS AND THAT Z GPRS3 Z UMTS Z LOGGER3 Z LTE WW THEIR FIRMWARE AND SOFTWARE ARE FREE OF ERRORS OR FUNCTIO...

Page 7: ...ddition to the time necessary to establish the connection from 5 to 30 seconds and the time due to any server login attempts When use PPP the internet connection is ALWAYS ON Check the data quantity s...

Page 8: ...wide UMTS HSDPA and GSM GPRS EDGE coverage 800 850 900 1900 2100MHz UMTS 850 900 1800 1900MHz GSM HSDPA Max 14 4Mbps DL HSUPA Max 5 76Mbps UL WCDMA Max 384Kbps DL Max 384Kbps UL EDGE Max 236 8Kbps DL...

Page 9: ...n be found in the installation manual for each product To consult the installation manual use link below Z LOGGER3 https www seneca it products z logger3 doc installation_manualEN Z GPRS3 https www se...

Page 10: ...n also be used for send logs alarms and send receive commands Z GPRS3 Z UMTS and Z LTE Z LTE WW can also send the last row of the log file via SMS An internal UPS is also available in UPS mode the RTU...

Page 11: ...WW Z GPRS3 Z UTMS Z LTE Z LTE WW support the following types of SIM CARDS Top up voice SIM CARD Subscription voice SIM CARD Data transmission only SIM CARD Zero cost operations can be run only on voic...

Page 12: ...1 106 2 97 3 88 4 79 5 70 6 61 7 MAXIMUM 52 Where 0 it s the minimum and 7 it s maximum For correct ftp or email log operations the minimum required field level is 2 7 please remember that signal oft...

Page 13: ...act your telephone service provider for GSM and GPRS service costs especially when using the RTU with a sim issued by a country other than the one in which it is used international roaming 6 INTERNAL...

Page 14: ...ty reason Z GPRS3 Z UMTS Z LTE Z LTE WW accept SMS command or audio call only from numbers present in the Address Book The address book is composed of a maximum of 8 telephone numbers emails Groups of...

Page 15: ...RTU will respond also if the telephone number isn t in the address book 7 2 MICROSDCARDPHONEBOOK ONLYZ GPRS3 Z UMTS Z LTE Z LTE WW It s possible to expand the internal phone book using a file in the m...

Page 16: ...embedded tags the maximum number of rows that can be stored in the internal flash is 16384 a new row will overwrite the oldest circular buffer Activating all the embedded tags and all 100 Extended Ta...

Page 17: ...4 WARN 02 06 2016 06 40 SYS PING Timeout 125 ERR 02 06 2016 13 14 PRT1 Bus Disconnected 126 ERR 02 06 2016 16 46 PRT1 Bus Disconnected 127 ERR 02 06 2016 19 48 PRT1 Bus Disconnected 128 ERR 02 06 2016...

Page 18: ...encryption using the Ethernet or GPRS Always ON PPP connection Z GPRS3 Z UMTS Z LTE Z LTE WW are compatible also with SMTPS server with TLS 1 2 encryption for example GMAIL but only with GPRS connecti...

Page 19: ...Bus Disconnected For events Digital1 and Digital2 alarm state for example INDEX LEVEL TIMESTAMP SOURCE MESSAGE 674 INFO 25 06 2016 00 18 23 SEC2 INPUT 2 ALARM ON 675 INFO 25 06 2016 00 18 23 SEC2 INP...

Page 20: ...csv Where xxxxxxx is an incremental number 8 2 THEDATALOGGERANDTHEDATALOGGERONTRIGGER The data logger works defining a Data acquisition time sample time The minimum sample time is 1 minute The board...

Page 21: ...0 0 0 1 1 43 43 42 44 51768 LOG 05 06 2016 14 40 0 0 0 0 0 0 1 1 43 43 42 44 Where INDEX is a progressive acquisition number LOG is a constant text TIMESTAMP is the Real Time Clock when the acquisiti...

Page 22: ...re the seconds of the first row data So the filename of the first example can be ZGPRS3TEST_log20160605143600 csv 8 2 2 Sending data logger and data logger on trigger data to an E MAIL server RTUs are...

Page 23: ...quisition is made The others values are the TAG name and variables declared by the user in the SEAL configuration The Data Logger on Trigger file when is open with excel is INDEX TYPE TRIGGER TIMESTAM...

Page 24: ...gyyyyMMddhhmmss csv Where RTUNAME is the name of the RTU yyyy is the year of the first row data MM is the month of the first row data dd is the day of the first row data hh are the hours of the first...

Page 25: ...The file name is different from the name that sent to the FTP EMAIL and it is Lxxxxxxx csv Where xxxxxxx is an incremental number 9 Sending data to an MQTT broker Data can be sent in real time using J...

Page 26: ...ays If you need to increase the number of log that can be stored you must format the microSD with the minimum allocation unit size In a dos shell cmd type format x FS FAT32 A 1024 Q Where x is the mic...

Page 27: ...DIO CALL and HTTP POST Example of messages are sending a text alarm Input 1 high ALARM when the analog input 1 is higher than 15 mA Audio messages are located into the AUDIO directories a preset of au...

Page 28: ...rver must be enabled from the SEAL software default is webserver OFF 13 1 MAINTENANCEWEBSERVER NOTE The webserver must be enabled from the SEAL software default is webserver OFF The maintenance webser...

Page 29: ...le to download or delete a single log file For debug you can see in real time all the external internal TAGs values in the Extended Variables Status Digital IO Analog IN Counters sections The last 16...

Page 30: ...accessing this webserver type in a browser with default ip address http 192 168 1 101 index html 192 168 1 101 must be replaced with the Ethernet or the Modem PPP IP address For example is possible to...

Page 31: ...date takes about 8 minutes The device must be connected to a PC with SEAL software installed Via microSD card A complete update takes about 20 seconds A microSD adapter for PC many mobile phones can a...

Page 32: ...ied to the main microSD folder 2 With the RTU OFF insert the microSD card in its slot 3 Turn ON the RTU 4 The SD STS led starts to flash at 1 second intervals for about 20 seconds The new firmware is...

Page 33: ...ration 2 Go to Build Generate 3 Now Seal will create 3 files seal debug tag 4 Connect to the webserver at address http ipaddress maintenance index html where ipaddress is the PPP modem or Ethernet IP...

Page 34: ...paddress maintenance index html where ipaddress is the PPP modem or Ethernet IP address 2 Go to the Upload File section 3 Under Configuration SEAL File select the seal file and then click UPLOAD 4 The...

Page 35: ...Us can activate a Modbus TCP IP Server and a Modbus RTU Slave on serial ports for accessing the Embedded and Modbus I O Server accepts up to 2 clients from Ethernet or Modem PPP connection The externa...

Page 36: ...RY GOOD 40009 8 DIGITAL OUTPUTS BIT READ ONLY Bit 14 DIGITAL OUTPUT 1 VALUE Bit 15 DIGITAL OUTPUT 2 VALUE 40015 14 CLOCK YEAR SIGNED 16 BITS READ ONLY Year 40016 15 CLOCK MONTH UNSIGNED 8 BITS READ ON...

Page 37: ...TS READ ONLY Most significant 16 bits 40091 90 Worktime 3 LSW UNSIGNED 16 BITS READ ONLY Value in Seconds Less significant 16 bits 40092 91 Worktime 3 MSW UNSIGNED 16 BITS READ ONLY Value in Seconds M...

Page 38: ...Example Value 40110 4 Bugfix Release 01 Minor revision 1 10 Build 10 40008 7 DIGITAL INPUTS AND SIGNALS BIT READ ONLY Digital Inputs Bit 0 INPUT1 VALUE Bit 1 INPUT2 VALUE Bit 2 INPUT3 VALUE Bit 3 INP...

Page 39: ...e 3 LSW UNSIGNED 16 BITS READ ONLY Less significant 16 bits 40076 75 Totalizer value 3 MSW UNSIGNED 16 BITS READ ONLY Most significant 16 bits 40077 76 Counter value 3 LSW UNSIGNED 16 BITS READ ONLY L...

Page 40: ...40219 40220 218 219 LONGITUDE FLOAT 32 READ ONLY Longitude 40221 40222 220 221 SPEED FLOAT 32 READ ONLY Speed 40223 40224 222 223 DISTANCE FLOAT 32 READ ONLY DISTANCE FROM CENTER 41003 41203 1002 1202...

Page 41: ...NAL FLASH TO microSD CARD 19 RESET LOG SESSION 20 ERASE ALL LOG FROM INTERNAL FLASH 16 FORCE MODEM RESET 65 STOP MODBUS TCP IP AND MODBUS RTU LOG 98 START MODBUS TCP IP AND MODBUS RTU LOG 97 DOWNLOAD...

Page 42: ...TE FAST COMMAND 15 63 CLOSE DIGITAL OUTPUT1 Write with Write Multiple Register write 32 in register 49001 write 32 in register 49002 write 512 in register 49003 OPEN DIGITAL OUTPUT1 Write with Write M...

Page 43: ...from Ethernet or 2G 3G connection For example is possible to connect a SCADA through Modbus TCP IP acquire directly the Modbus RTU I O slaves registers 1 The SCADA start with a Modbus TCP IP Request...

Page 44: ...s possible to access the RTU webserver with http senecazumts ddns net index html The IP can change but name is always the same Also the RTU Modbus TCP IP server can be reached for example configuring...

Page 45: ...Status from all counters GET DINn All nth input counter status GET DINn TOT All nth input totalizers status GET DINn CNT All nth input counters status RESET DIN Reset all counters RESET CNTn Reset th...

Page 46: ...PPO 345 Write 345 to the PIPPO extended variable SMS COMMANDS FOR DIGITAL OUTPUTS SET DOUTn OPEN Opens the nth digital output SET DOUTn CLOSE Closes the nth digital output SET TOGGLEn Toggle the nth d...

Page 47: ...reshold analogue input 1 or 2 SET AIN DELAY TIME_ON_OFF Set time filter on threshold activation for analogue input 1 0 2 SMS COMMANDS FOR GPS SETTINGS FOR Z LTE Z LTE WW Z UMTS INSTRUMENTS ONLY GPS GO...

Page 48: ...FTP connection settings path the FTP server folder where files are sent name_ip IP address or FTP server name port FTP server gateway user FTP server login user name password FTP server login passwor...

Page 49: ...email with the internal temperature sensor value EMAIL SYSLOG Send the last week syslog csv log file on microSD via email first administrator address in the address book FTP SYSLOG Send the last week...

Page 50: ...TP download folder the firmware AND the setup file Then if the release is different from the installed the firmware and the configuration are updated The firmware name must be fwupdt bin The setup nam...

Page 51: ...am execution setting ALL dip switches to ON at boot up This emergency mode is useful if a SEAL program does not allow to connect to SEAL for example because the board will reboot continuously In emerg...

Page 52: ...UBLESHOOTING PROBLEM SOLUTION Sending the SMS command email test no email reaches the administrator s email address Make sure the set APN corresponds to the mobile service provider s and whether acces...

Page 53: ...GSM signal is always 0 7 and the GSM led continues to flash fast The inserted SIM is not recognised Clean or replace the SIM The SIM PIN is enabled Insert the SIM in a mobile phone and disable the PIN...

Page 54: ...contact the NTP server Make sure that the UDP port 123 is open Check the configured NTP server address The device is unable to send emails or ftp files on the Internet through the Ethernet port but a...