User Manual
T201DCH50/100/300/600-MU
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc. MI00546-EN
Rev.2
Page 24
WARNING!
The Output Voltage is limited to about 10.8V
If The Output is configured in “Digital”:
Digital Ouput Type:
Select between Normally Low or Normally High.
Alarm Type:
Select Between:
NONE:
No Alarm active
MAXIMUM
: Alarm if the Current is above the High Threshold
MINIMUM:
Alarm if the Current is below the Low Threshold
ACTIVE IF INTO THE WINDOW:
(Alarm if the Current > Low Threshold but < High Threshold)
ACTIVE IF OUT THE WINDOW:
(Alarm if the Current is > High Threshold or < Low Threshold)
Alarm Delay:
Select the Alarm delay in x 10 ms (for example write 100 for 1 second delay)
Hysteresis:
Select the Alarm Hysteresis in [A]
High Alarm:
Select the High Threshold for the Alarm in [A]
Low Alarm:
Select the Low Threshold for the Alarm in [A]