USER MANUAL – Z-TWS4/Z-PASS2-S/S6001-RTU
202
This function returns the current number of minutes since January 1, 2000
0:00:00, if DATETIME is empty or DATETIME is not a valid date/time; otherwise,
it returns the number of minutes since January 1, 2000 0:00:00,
corresponding to DATETIME.
DATETIME shall have the following format:
"dd/mt/yyyy hh:mm:ss"
19.2.4
MBUS_READ_CTL
The MBUS_READ_CTL function can be used to enable/disable the M-Bus read
operations.
It should be noticed that M-Bus read operations are enabled by default.
The function has the following input parameter:
- ENABLE : TRUE, to enable read operations
FALSE, to disable read operations
The function has the following output parameter:
- RESULT : 1: function has been successfully executed
-1: function execution failed