PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT:
PRG-SE-C -O1
TECHNICAL SHEET 1/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON
S
ISTEMAS
E
LETRÔNICOS DE
C
ONTROLE
L
TDA
.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel/Fax:
(55 11) 3019-1616
http://www.selcon.com.br
1/6
SELCON
Automação Industrial
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
February/10
Representative or Distributor
•
A
PPLICATION
Programmer PRG-SE-C -O1 equipment recommended for start, flame supervision and safe
stop for any type of burner for one stage of flame, in applications commercial or industrial and
gas Fuels or liquids light, with a cycle of
use do not continuum
(on/off burner Period in less
than 24 hours). For use in camera of combustion closed, the user is the river system must
provide insurance pre-purge before each sequence of start, or require the programmer PRG-SE-
C -O1 with purge timer coupled, since that the times offered are appropriate for application.
Entry for flame sensor for ionization. See electrode sensors for ionization, line SEL-HT-I
(standard) or SEL-HT-E (electrode mounted on a drawing or sample of the client).
This product meets the requirements of the standard NBR 12313 of ABNT-
review Sept./2000.
•
T
ECHNICAL
D
ATA
⇒
⇒
⇒
⇒
Watch dog micro process – to provide safe failure.
⇒
⇒
⇒
⇒
Supply / frequency: 90 a 250 Vca - 50/60 Hz
±
3%.
NOTE: To supply network consisting of phase/neutral, should consider the
possible need for its reversal (terminals 5 and 6) for flame sensor circuit
not lose sensitivity and therefore the capacity to detect signal of flame.
⇒
External Fuse: Foresee fuse for internal circuits’ protection in accordance to the
foreseen load in the project, respecting the boundaries of this specification.
⇒
⇒
⇒
⇒
Consumption of energy: 4 VA
⇒
⇒
⇒
⇒
Protection against tension outbreaks
⇒
⇒
⇒
⇒
Fuses: The designer/user has should consider the use of two external fuses,
one for protection of the internal circuits of the PRG-SE-C -O1 (250 mA
retardate), and another of protection the outputs of the circuits in accordance
with the load specified in the project, within the limits of this Specification. O
programmer PRG-SE-C -O1 do not own internal fuse.
⇒
⇒
⇒
⇒
Temperature of work : 0 a 60ºC
⇒
⇒
⇒
⇒
Storage ambient temperature:
-
5° a 65 °C
⇒
⇒
⇒
⇒
Maximum relative humidity of environment in operation: 90% (40 ± 2°C) – NBR 5291
⇒
⇒
⇒
⇒
Flame Sensor: Ionization.