Selcon PRG-SE-C O1 Series Technical Sheet Download Page 1

PROGRAMMER FOR START, FLAME SUPERVISION  

AND SAFE STOP OF BURNER 

PRODUCT:

 

PRG-SE-C -O1

                                      

TECHNICAL SHEET 1/6 

  

 Costumer Service 55 11 3019-1616

                                

For further details see technical bulletin

 

 

SELCON

 

S

ISTEMAS  

E

LETRÔNICOS DE 

C

ONTROLE 

L

TDA

.

 

CNPJ 56.935.877/0001-29 

Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho •   São Paulo • SP • Tel/Fax: 

(55 11) 3019-1616 

http://www.selcon.com.br 

 

 

 

1/6 

  

SELCON

 

 

Automação Industrial

 

Selcon Ltda., keeps the right to modify this technical sheet  

when never it is necessary

 

February/10

 

 

Representative or Distributor 

 

A

PPLICATION

 

     Programmer  PRG-SE-C -O1  equipment  recommended  for  start,  flame  supervision  and  safe 

stop  for  any  type  of  burner  for  one stage  of  flame,  in applications  commercial  or  industrial  and 
gas  Fuels  or  liquids  light,  with  a  cycle  of 

use  do  not  continuum

  (on/off  burner  Period  in  less 

than  24  hours).  For  use  in  camera  of  combustion  closed,  the  user  is  the  river  system  must 
provide insurance pre-purge before each sequence of start, or require the programmer PRG-SE-
C -O1  with  purge  timer  coupled,  since  that  the  times  offered  are  appropriate  for  application.  
Entry  for  flame  sensor  for  ionization.  See  electrode  sensors  for  ionization,  line  SEL-HT-I 
(standard) or SEL-HT-E (electrode mounted on a drawing or sample of the client). 
    

 

This  product  meets  the  requirements  of  the  standard  NBR  12313  of  ABNT-

review Sept./2000. 

 

 

T

ECHNICAL 

D

ATA

 

 

  

Watch dog micro process – to provide safe failure. 

 

Supply / frequency: 90 a 250 Vca - 50/60 Hz 

±

 3%. 

NOTE: To supply network consisting of phase/neutral, should consider the 

possible  need  for  its  reversal  (terminals  5  and  6)  for  flame  sensor  circuit 

not lose sensitivity and therefore the capacity to detect signal of flame. 

 

External  Fuse:  Foresee  fuse  for  internal  circuits’  protection  in  accordance  to  the 
foreseen load in the project, respecting the boundaries of this specification.  

 

Consumption of energy: 4 VA 

 

  Protection against tension outbreaks 

 

Fuses:  The  designer/user  has  should  consider  the  use  of  two  external  fuses, 

one  for  protection  of  the  internal  circuits  of  the  PRG-SE-C -O1  (250  mA 

retardate), and another of protection the outputs of the circuits in accordance 

with the load specified in the project, within the limits of this Specification. O 

programmer PRG-SE-C -O1 do not own internal fuse. 

 

Temperature of work : 0 a 60ºC 

 

Storage ambient temperature:

 -

5° a 65 °C 

 

Maximum relative humidity of environment in operation: 90% (40 ± 2°C) – NBR 5291 

 

Flame Sensor: Ionization.  