Generator Controller

Installation Manual

!

4560 River Bottom Drive 
Norcross, GA 30092 
P: +1-770-455-9110 
W: SELCOUSA.com 

Summary of Contents for C6200 FlexGen

Page 1: ...C6200 FlexGen Generator Controller Installation Manual 4560 River Bottom Drive Norcross GA 30092 P 1 770 455 9110 W SELCOUSA com...

Page 2: ...ts 12 5 5 Analogue Inputs 14 5 5 1 Voltage Input 14 5 5 2 Frequency Input 14 5 6 Parallel Lines 15 5 7 GOV AVR Control 16 5 8 Inputs 18 5 8 1 C B 18 5 8 2 Manual 18 5 8 3 Unload 18 5 8 4 Reset 18 5 8...

Page 3: ...on check and automatic synchronisation voltage matching active and reactive load sharing basic and programmable I O and data acquisition The Littelfuse Selco C6200 FlexGen can operate in parallel with...

Page 4: ...Selco C6200 FlexGen Revision 03 06 2014 Page 4 of 24 2 Front View...

Page 5: ...f the switch board using four 5 mm screws DIN rail mounting is not advisable due to the weight Please ensure that enough space is given around the module so that the plug in terminals can be removed a...

Page 6: ...vessels hull is considered as ground Connecting any of the COM connections on the C6200 FlexGen to ground hull or switchboard chassis may cause electrical noise to be injected into the system The gene...

Page 7: ...vide a nominal voltage of 24 V DC The C6200 FlexGen will tolerate relatively wide variations in the supply voltage please refer to the specifications The supply is connected to terminal 30 and 32 of t...

Page 8: ...The generator should be stopped and blocked against starting the busbar should be dead Also make sure that there is no risk of another power source being connected to the busbar while you are working...

Page 9: ...ltage Generator phase L2 7 AC voltage Generator phase L3 The BUSBAR VOLTAGE LED shows by steady light whether the voltage levels measured between the phases are within limits The reference is the nomi...

Page 10: ...s are isolated by e g transformers inside the third party equipment The CT ratio should cover the maximum current of the generator The CTs must be capable of coping with limited time short circuit cur...

Page 11: ...a connection between S1 and S2 before you disconnect the CT cables from the GENERATOR CURRENT terminals Please note that incorrect connection of the current transformers e g by reversing the terminals...

Page 12: ...lexGen Configuration Manual Terminal Signal Description 15 NO contact to COM Programmable input 1 16 NO contact to COM Programmable input 2 17 NO contact to COM Programmable input 3 18 NO contact to C...

Page 13: ...lco C6200 FlexGen Revision 03 06 2014 Page 13 of 24 Programmable inputs and outputs used for control of conventional speed governor Programmable inputs and outputs used for load depending start and st...

Page 14: ...nected to terminal 32 Supply minus In rare situations gound loops can cause noise to be injected into the application Ground loops happen when multiple COM connections between modules e g parallel ope...

Page 15: ...ignal Description 27 DC voltage kW BALANCE of other FLEXGEN modules 28 Common reference COM of the other FLEXGEN modules 29 DC voltage kVAr BALANCE of other FLEXGEN modules Please note that terminal 2...

Page 16: ...current input 36 DC voltage Governor voltage input 37 reference isolated AVR reference 38 PWM signal AVR PWM input 39 DC current AVR current input 40 DC voltage AVR voltage input It is important to n...

Page 17: ...7 of 24 C6200 FlexGen controlling electronic speed governor by a DC voltage C6200 FlexGen controlling ECU by a PWM signal Note that the amplitude of the PWM signal is determined by the configuration o...

Page 18: ...perational situation of the system 5 8 2 Manual Activating the manual input will prevent the C6200 FlexGen from interfering with the speed and voltage controls of the generator unless it gets a comman...

Page 19: ...on Breaker remote close 48 Relay contact Signal source 49 Relay energized position Breaker remote close 5 9 2 Protection Trip The protection trip relay is a change over relay intended for tripping the...

Page 20: ...inal 64 REF The outputs are used for indication and control of external equipments e g common alarms or speed voltage control relay pulses Terminal Signal Description 56 Normally open relay output Pro...

Page 21: ...n applies between the output resistor and the internal resistance of the driven equipment Example equipment with an internal resistance of only 10 k would reduce a 10 VDC output voltage to 5 VDC The t...

Page 22: ...toggeling DIP switch 5 to ON position The termination resistor must be enabled only on the first and on the last unit on the RS485 bus The maximum cable length for RS485 is 1 000 meters The cable must...

Page 23: ...23 AWG22 Cable resistance should be less than 26 m per meter The first and the last module on the CANbus need a termination resistor 150 between lines A and B It is not necessary to connect external r...

Page 24: ...mbient temp range 20 C 70 C Vibration IEC 60068 2 6 Humidity IEC 60068 2 30 EMC IEC 61000 4 3 2006 IEC 61000 4 6 2004 IEC 61000 4 5 2005 IACS E10 2006 Test No 15 CISPR 16 1 1999 CISPR 16 2 2002 Relay...