6. Technical Data
Order Number
42702001
Cooling Capacity L35L35
600 W @ 50 Hz
600 W @ 60 Hz
Cooling Capacity L35L50
300 W
Compressor
Rotary piston compressor
Refrigerant / GWP
R134a / 1430
Refrigerant Charge
265 g / 9.3 oz
High / Low Pressure
30 / 9.1 bar
435 / 132 psig
Operating Temperature Range
+10°C - +50°C
Air Flow Volume (System / Unimpeded)
Ambient air circuit: 340 / 650 m³/h
Cabinet air circuit: 170 / 550 m³/h
Mounting
Wall mounted / Recessed
Housing Material
Mild steel, powder coated
Dimension A x B x C (D+E)
810 x 395 x 145 (25+120) mm
Weight
33 kg
Cut Out Dimension
791 x 376 mm
Voltage / Frequency
400 / 460 V - 50/60 Hz 2~
Current L35L35
1.5 A
Starting Current
4 A
Max. Current
2.1 A
Nominal Power L35L35
550 W @ 50 Hz
570 W @ 60 Hz
Max. Power
700 W
Fuse
2 x 3 A (T)
SCCR
5 kA
Connection
Connection terminal block
Ingress Protection
IP 54
Approvals
CE, cURus, cULus