14. Maintenance & Cleaning

Danger from electrical voltage
Maintenance and cleaning must be carried out by specialists (electricians). The
personnel must ensure that for the duration of this work the unit and the cabinet
are disconnected from the electrical supply and protected against unauthorised
reactivation.

Danger through incorrect work on the unit
The instructions in the cabinet manufacturer’s manual must be read.

Damage to the unit through incorrect maintenance and repair.
Maintenance and repair of the refrigerant circuit must be carried out by the
manufacturer or another specialist.

Unit service and cleaning 
All units are virtually maintenance-free. 
Note: Please check on our website under download / service and maintenance for our new videos.

However, the following points must be taken into account:
The service and cleaning of the unit must be undertaken by specialists. The personnel must ensure that for the
duration of the cleaning work the unit and the cabinet are disconnected from the electrical supply and protected
against unauthorized reconnection. The connections 1&2 and 3&4 are not low voltage (<50V).

Regularly check the condenser profile for dirt tests (approx. every 2,000 hours depending on the grade of
ambient pollution).

Should the condenser need cleaning: 
Disconnect the whole plant from the mains.

Clean the condenser profile as required by blowing it out with compressed air.
In cases of extreme pollution a cleaning fluid must be used.

Danger from electrical voltage.

The unit must be removed from the control cabinet for wet cleaning! Instruction: Never use aggressive
cleaning fluids or materials.

Should fluid cleaning be necessary: 
Disconnect the whole plant from the mains

Remove the unit from the cabinet
Ensure that the seals are not damaged
Remove the radial fan
Steam-clean the condenser profile or wash it with an environmentally safe cleaning fluid.

Instruction:After cleaning and drying the unit, there must be a two hour delay before the unit is taken back
into operation.

15. Maintenance

Attention! Only use original replacement parts when repairing the unit. This ensures that the unit functions
perfectly and remains safe.  For further information and spare part ordering please contact us by email under on
one of the addresses stated on the last page.

Radial fan replacement: The normal working life of the fan is app. 40,000 working hours under normal

Summary of Contents for 42690001

Page 1: ...3 4 Settings 4 5 Functional Principle 4 6 Technical Data 5 7 Mounting 6 8 Condensate management 8 9 Mounting Principle 9 10 Electrical Connection 10 11 Wiring Diagram 12 12 Taking into Operation 13 13...

Page 2: ...ons in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage...

Page 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Page 4: ...vironmental ratings please refer to the type plate data 5 Functional Principle The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main components compress...

Page 5: ...50 C Air Flow Volume System Unimpeded Ambient air circuit 250 650 m h Cabinet air circuit 125 250 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimension A x B x C D E 6...

Page 6: ...irit level that the cabinet is in a horizontal position The max deviation from the vertical or horizontal is 3 degrees Air apertures To provide adequate air circulation and avoid temperature layers fr...

Page 7: ...the surface of the cabinet and remove the mounting template Stick the self adhesive unit seals on the outer surface of the cabinet for externally mounting and on the inner surface of the cabinet for...

Page 8: ...The condensation drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the b...

Page 9: ...4 05 2021 Doc No 9942690001 9 17 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 Mounting gasket 2 Mounting clip 3 M6 slotted set screw 4 Washer 5 Lock nut Fig 1 Recesse...

Page 10: ...external components it must be ensured that the wiring and connections are double insulated and safe against touch and protected from unauthorized and or accidental external contact Ensure that the co...

Page 11: ...minals T1 T2 Connect the door contact switch to terminals T1 T2 The contact must be closed when the cabinet door is closed SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit...

Page 12: ...Version No 1 3 04 05 2021 Doc No 9942690001 12 17 11 Wiring Diagram...

Page 13: ...on the PC board slightly to the right higher or to the left lower Close the unit in the prescribed manner Check that the new adjusted values meet the necessary requirements If necessary repeat the pr...

Page 14: ...Install the unit at a di erent place The ambient temperature must be within the stated operating temperature range The control cabinet is not sealed properly The control cabinet needs re sealing Fan o...

Page 15: ...ction The connections 1 2 and 3 4 are not low voltage 50V Regularly check the condenser pro le for dirt tests approx every 2 000 hours depending on the grade of ambient pollution Should the condenser...

Page 16: ...fan xing screws Connect the fan cable to the PC board and replace the board if necessary Dispose the old fan according to the environmental laws and regulations 16 Transport Storage Malfunction due t...

Page 17: ...rt Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown W...

Reviews: