Section 3: Testing
Testing the Sacksafoam
Sacksafoam II Model 8044 Operations Manual
(Version C)
8
Wet Test
1.
For the wet test, foam or water can be used for test purposes.
2.
Place a full 5 USG container of fire-retardant foam in the space provided within the Sacksafoam
case.
3.
Insert the dip tube into the foam container and press
the rubber stopper down to seal the filler neck.
Push the dip tube down to contact the bottom of the
container.
4.
If you are using foam for the test, place a break away hose into the empty container.
5.
Turn the controller on and set the dispense time to 10.
6.
Activate the dispense switch.
7.
The pump should now start. There may be a short delay until the pump primes itself. To complete
the test, activate the dispense switch a second time. Foam or water should flow for 10 seconds.
8.
Once the test is finished, store the dip tube as shown
in the photo.