Technical Information
GDH Series Direct Fired Ducted Heater
Page 11 of 16
GDH Selection Table
The prefix ‘GDH’ indicates gas duct heater. Number following indicate Model capacity in megajoules per
hour (MJ/h). Heating air flow is rated at 14 m/s velocity over the burner with a pressure drop through the
heater of 125 Pa.
Application examples for GDH heaters and AL Series coolers:
Table 1 - Models with Dampers
For installations requiring reduced air flow on heating, cooler runs on high speed for heating and cooling.
Lower air flow for heating is effected by dampers closing to about one third of high speed air flow.
GDH
Model
Nominal
Cooler Match
Cooling Air l/s
Heating Air l/s
kW @
1.75 kPa
kW @
1.12 lPa
Min
Max
Min
Max
1500
AL36
15,000
21,000
7,000
11,000
440
293
1100
AL30
10,000
14,500
4,500
7,000
259
172
340
AL25
6,500
9,500
2,200
4,500
132
94
265
AL22
4,000
6,400
1,400
2,200
1+10
75
210
AL18
2,800
4,500
900
1,400
87
58
Table 2 - Models without Dampers
For installations requiring the same air flow for heating and cooling
GDH
Model
Nominal
Cooler Match
Air Quantity L/s
kW @
1.75 kPa
kW @
1.12 kPa
Min
Max
2500
AL33/36
20,000
15,000
732
-
2110
AL30
14,500
9,000
586
390
1585
AL25
8,800
6,000
440
293
1055
AL22
5,800
4,400
293
176
790
AL18
4,200
2,400
220
148
525
AL15
2,200
1,500
117
100