INSTALLATION INSTRUCTIONS

MR-2602A/2605A 
Class A Zone Input Module

The MR-2602A Zone Input module converts the two zones on the MR-2602 fire alarm 
control panel from Class ‘B’ Style ‘B’ to Class ‘A’ Style ‘D’. The MR-2605A Zone Input 
module converts the five zones on the MR-2605 fire alarm control panel from Class ‘B’ 

Style ‘B’ to Class ‘A’ Style ‘D’.

SPECIFICATIONS

Voltage:  24 V

DC

 (nom)

Standby current:  MR-2602A ... 2 mA, MR-2605A ... 5 mA

Alarm current:  60 mA (max)

Loop Resistance:  100 W (max)

Devices per zone:  20 @ 100mA each

NOTE: 

This component must be included in the control panel battery calcula-

tion. Refer to the Standby Battery Calculation Sheet (PN# 29005850) 
included with the control panel.

MR-2602A

MR-2605A

Limited Warranty

Secutron warrants that for a period of five years from the date of purchase, the product 
shall be free of defects in material and workmanship under normal use and that in ful-
fillment of any breach of such warranty, Secutron shall, at its option, repair or replace 
the defective equipment upon return of the equipment to its repair depot. This warranty 
applies only to defects in materials and workmanship and not to damage incurred in 
shipping or handling, or damage due to causes beyond the control of Secutron such 
as, lightning, excessive voltage, mechanical shock, water damage or damage arising 
out of abuse, alteration or improper application of the product.

The foregoing warranty shall apply only to the original buyer, and shall be in lieu of any 
and all other warranties, whether expressed or implied and of all other obligations or 
liabilities on the part of Secutron. This warranty contains the entire warranty. Secutron 
neither assumes responsibility for, nor authorizes any other person purporting to act on 
its behalf to modify or to change this warranty, nor to assume for it any other warranty 
or liability concerning this 
product.

In no event shall Secutron be liable for any direct, indirect or consequential damages, 
loss of anticipated profits, loss of time or any other losses incurred by the buyer in con-
nection with the purchase, installation or operation or failure of this product.

Important!

Secutron recommends that the entire system be completely tested on a regular 
basis. However, despite frequent testing, and due to but not limited to criminal 
tampering or electrical disruption, it is possible for this product to fail to perform 
as expected.

Secutron Inc.
25 Interchange Way
Vaughan, Ontario, Canada
L4K 5W3

Tel: (905) 695-3545
Fax: (905) 660-4113
www.secutron.com

60 Industrial Parkway
Cheektowaga, NY, 14227
Tel: 1-888-SECUTRON
Fax: 888-660-4113 