EPI-BUS devices
Mounting and installation, Technical Description, T 811 086 en e
77 / 128
8.5
B5-EPI-ASP-GS alarm scrolling panel for the Netherlands
Via the
Extended Bus
(EPI-BUS) by means of a patch cable and an
8-pin RJ45 plug, the Dutch fire brigade panel can be connected to
any SecuriFire MIC11 / MIC711 as well as to the B5-MMI-FIP and
B5-MMI-IPS devices.
Additional EPI devices can be connected to the second RJ45.
The B5-EPI-ASP-GS is mounted either on the door of the Securi-
Fire or immediately next to a remote SecuriFire indication and con-
trol map.
Via the hex coding switch you can set one of the three possible
EPI-BUS addresses. For each MMI-BUS participant with an EPI-
BUS interface, up to three EPI devices can be connected.
More information about the B5-EPI-ASP-GS can be found in the
Technical Description T 811 090.
Fig. 99 B5-EPI-ASP-GS
8.5.1
Interfaces
EPI Port A “INCOMING”
EPI Port B “OUTGOING”
Designation
Terminal
Terminal
Designation
GNDP
1
2
VP
3
4
EXTBUS-
+3V3
5
6
+3V3
GNE
7
8
GND
8.5.2
Technical data
Operating voltage:
3.3 V
Quiescent current:
0 mA
Data transmission:
Electrical:
EPI bus
RS485
Distance to the MIC main indication and control map:
max. 1 m
Protection class:
IP30
Ambient temperature:
-5°C to +50°C
Dimensions:
Dimensions without map case:
170 x 138 x 48 mm (W x H x D)
85 x 70 x 20 mm (W x H x D)
Map case colour:
grey
8.5.3
Compatibility information
SecuriFire Studio
from release 1.0
EPI interface
B5-MIC (all versions), B6-MIC (all versions)
B5-MMI-FIP, B5-MMI-IPS
Notice
From which side the EPI bus “INCOMING” or
“OUTGOING” is connected is not relevant.
For purposes of clarity, however, we recommend
continuing with one connection system once be-
gun.