Expansion units for SecuriFire 2000
Mounting and installation, Technical Description, T 811 086 en e
43 / 128
6.6
B4-EIO input/output unit
If required, the B4-EIO can be fitted on the B6-BCB13 main control unit of the SCP2000.
The B4-EIO includes 10 monitored inputs and 8 monitored outputs as well as the control electronics for a LED display panel.
6.6.1
Interfaces
X1
B6-BCB13 connector plug
X2, X3
Connector plug for detection zones and inputs
X4
Connector plug for monitored outputs
X5
Connector plug for LED display panel
X11
– X20
Jumpers for setting the inputs
X111
– X182
Jumpers for adjusting the monitored outputs
Fig. 51 B4-EIO interfaces
6.7
Connector plugs for detection zones and inputs (X2, X3)
On interfaces X2 and X3, 10 primary inputs or 10 detection zones can be connected (any combination). Every input/line has
its own current-limited output driver which supplies the connected peripheral devices with power.
The operation mode and subtype selection is carried out individually for each detection zone and input. This is accomplished
by means of planning software (SecuriFire Studio) and with jumper settings on the unit. If the jumper setting does not match
the planning, a fault is reported on the SCP after startup.
The following functions can be planned for each input:
Input monitored 26k7
VdS interface
Input DFG-60 BLK3
Valve monitoring
Input monitored 3k
Series 130/A with pre-alarm
Series 130 Ex-i
SecuriStar 521 / 523 / 563, LKM583, with pre-alarm
Series 130A, MCP, without pre-alarm
SecuriStar 521 / 523 / 563, LKM583, without pre-alarm
SLR-E-IS
DCD-1E-IS