Expansion units for SecuriFire 2000
42 / 128
Mounting and installation, Technical Description, T 811 086 en e
6.5
Connector plug for monitored outputs (X4)
The B6-EIO input/output unit is suitable for connecting 8 primary outputs. Every output has its own current-limited output
driver which supplies the connected output with power. The outputs are selectively monitored for short-circuits and wire
breakage (according to EN54-13). The setting of the load range has to be planned exclusively with software (SecuriFire Stu-
dio).
Connection:
loads 20
to 1000
, divided into 3 load ranges
Output voltage:
24 VDC (22
VDC …28 VDC)
Output current:
max. 1.3 A
6.5.1
Connection assignment for plug (X4)
Output no.
Designation
Terminal
8
OM8 -
1
OM8+
2
7
OM7 -
3
OM7+
4
6
OM6 -
5
OM6+
6
5
OM5 -
7
OM5+
8
4
OM4 -
9
OM4+
10
3
OM3 -
11
OM3+
12
2
OM2 -
13
OM2+
14
1
OM1 -
15
OM1+
16